Daikin ATM18MV2S Manual de serviço - Página 11
Procurar online ou descarregar pdf Manual de serviço para Manipuladores de ar Daikin ATM18MV2S. Daikin ATM18MV2S 20 páginas. Removal procedure, 5.0/6.0/7.1 kw class, 15000/18000 btu/h class
Também para Daikin ATM18MV2S: Manual de serviço (20 páginas)
![Daikin ATM18MV2S Manual de serviço](/uploads/products/server2/1533248/1533248.jpg)
Si041254EE
Step
7
Disconnect the
connector [S1].
8
Disconnect the
connectors [S6] and
[S8].
9
Remove the screw of
the electrical box.
10
Unfasten the hook at
the back of the
electrical box.
11
Pull out the electrical
box.
Removal Procedure
All manuals and user guides at all-guides.com
Procedure
Points
[S1]: fan motor
[S1]
(R2774)
[S6]: swing motor for horizontal
blades
[S8]: swing motor for vertical
[S6]
blades
Some models do not have
the harness for [S8].
[S8]
(R2775)
Electrical box
(R3205)
Hook
When reassembling, make
sure that the hook at the
back of the electrical box is
fastened.
(R17665)
Electrical Box
9