Adjustments
Two trimpots on the
back of the sensor
Remove
sensor
are used to adjust
from
bracket
the Daylight Hold-
Off threshold and
PIR mo on sensor
Attach
sensor
sensi vity. For easier
to
bracket
access to the trimpots
a er the sensor
has been mounted,
remove the sensor
from the moun ng bracket.
Use cau on when adjus ng the trimpots.
Do not use excess force, as this will damage the unit.
Stop turning the trimpot when you feel resistance.
PIR Sensi vity
Turn the trimpot clockwise to increase sensi vity.
Turn the trimpot counter-clockwise to decrease.
Daylight Hold-Off (op onal)
The sensor is shipped with the Daylight Hold-Off op on disabled
(trimpot at the maximum se ng, fully clockwise). When disabled it
will not hold off the lights when the space is occupied.
1. Ensure that the light level is low enough that
electric lights are required.
2. Set the trimpot so the threshold is at the
minimum level, fully counter-clockwise;
lights are always being held off .
3. Momentarily press the U lity bu on to ac vate installa on test
mode. The red LED fl ashes to indicate mo on detec on, the
Network LED (green) should be ON.
4. Slowly adjust the trimpot un l the Network LED (green) goes off .
At this se ng, a er the sensor is added to CSM, when the
light is below this level occupancy will turn on the electric
lights in the zone.
5. Momentarily press the U lity bu on to exit installa on test
mode.
Copyright © 2012, Daintree Networks, Inc.
All rights reserved.
ZigBee® is a registered trademark of the ZigBee Alliance.
Daintree Networks, Inc.
1503 Grant Road, Suite 202, Mountain View, CA 94040
(p) +1 (650) 965 3454 (e) [email protected] (w) www.daintree.net
page 4 of 4
To test the daylight hold-off a er the installa on is complete and
the sensor has been added to CSM:
1. Ensure that CSM's control strategy for this zone makes use of
occupancy sensors and has the 'Enable Daylight hold-off ' check
box selected.
2. Wait un l vacancy is detected and the lights turn off .
3. Trigger occupancy while the light level is below the selected
threshold. The lights should turn on.
Trigger occupancy while the light level is above the selected
threshold. The lights should remain off .
Troubleshoo ng
No LEDs turn on when I press the U lity bu on.
• Check ba ery installa on.
• Make sure ba eries are oriented (+ -) correctly.
The red Infrared Detec on LED does not ac vate when walking
through the coverage area while in Installa on Test mode.
• Check to see if the red LED turns on when you wave your hand
Minimum
Maximum
(counter-
(clockwise)
– If the red LED turns on, adjust the PIR Sensi vity trimpot
clockwise)
– If the red LED does not turn on, the Installa on Test mode
The red LED fl ashes when nobody is moving in the coverage area.
Minimum
Maximum
• Adjust the PIR sensi vity trimpot counter-clockwise to reduce
(counter-
(clockwise, disable
clockwise)
daylight hold-off)
• Check for sources of hot air fl ow in the coverage area.
• Review the Placement guidelines and eliminate false trigger
If lights do not turn Off a er the WOS2-WM has Joined the ZigBee
network:
• Check the "Off delay" for the zone in the Daintree CSM.
• Check for other CSM scheduled events or manual overrides that
may be keeping the lights On.
FCC warning
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protec on against harmful
Interference when the equipment is operated in a commercial
environment. The equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruc on manual, may cause harmful interference to radio
communica ons. Opera on of the equipment in a residen al area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his/her own expense.
www.daintree.net
directly in front of the lens.
clockwise to increase sensi vity. Check for objects or barriers
obstruc ng the sensor's view of the coverage area.
may have med out. Restart the Installa on Test mode by
momentarily pressing the U lity bu on. The green LED turns
on briefl y, then the red LED fl ashes with each detec on.
Installa on Test mode mes out in 5 minutes.
sensi vity. Repeat the walk test.
sources.
WOS2-WM 120731