DSC PowerSeries PC5108FLR Instruções de instalação
Procurar online ou descarregar pdf Instruções de instalação para Sistema de segurança DSC PowerSeries PC5108FLR. DSC PowerSeries PC5108FLR 2 páginas.
PC5108FLR v2.0 Installation Instructions
8 Zone Expander Module
This Installation sheet shall be used in conjunction with the Installation Manual of the
DSC equipment to which PC5108FLR is connected or powered from (e.g. alarm controller,
power supply, etc.). The PC5108FLR module can be used to extend up to 8 hardwired fast
loop response zones on the compatible DSC Alarm Controllers, models PC5020, PC1864,
PC1832 and PC1616. The fast loop response will be approximately 25ms.
General
PC5108FLR may be installed in the same metallic cabinet as the alarm controller/power
supply (model Power UC1, PC5003C) or in a separate enclosure (PC4003C). Internal and/
or external wiring for the PC5108FLR shall be routed, supported, clamped or secured in a
manner that reduces the likelihood of (a) excessive strain on wire and terminal connections
(b) loosening of terminal connections and (c) damage of conductor insulation.
Specifications
•Temperature range: -10°C to + 55°C
•Relative Humidity: 93% non condensing
•Input rating: 12V
/135mA (provided by the alarm controller or separate power supply)
DC
•Board current draw: 35mA (set and unset state)
•Board dimensions: 45mm x 92mm
•VAUX output ratings: 12V
, -15%/ +10% when Input voltage is between 85%
DC
to110% of rated value and output current is between 0mA- 100mA max.
•Ressetable fuse (PTC) used on circuit board instead of replaceable fuses
Terminal Descriptions
J6
ON
SW1
OFF
OFF
J4
J5
TAM
VAUX
RED BLK YEL GRN
Z1 COM Z2
TO COM
VAUX
12V
DC, LIMITED
AT 100mA
TO DEVICES
REQUIRING POWER
KEYBUS TO
RED
PRECEDING
EXPANSION
BLK
MODULE OR
CONTROL
YEL
PANEL
GRN
Used to tamper the cabinet in which the PC5108FLR is mounted. Connect a nor-
TAM -
mally closed (NC) switch across TAM and BLK. If the tamper is not being used connect a
piece of wire across TAM and BLK to remove the trouble condition.
29 0 0 7 4 9 2 R0 0 1
There is a built-in tamper switch on the expander module located in the top left corner of
the circuit board. If the cabinet in which the PC5108FLR is mounted has the hardware
required to depress this tamper switch, do not connect anything to the TAM terminal.
- Used to provide power for devices. Maximum current draw is not to exceed 100
VAUX
mA. Connect the positive lead of powered devices to VAUX and the negative to BLK or any
COM terminal.
- The 4 wire KEYBUS connection is used by the panel to communicate with the
KEYBUS
module. Connect the RED, BLK, YEL and GRN terminals to the KEYBUS terminals on the
PC1616, PC1832, PC1864 & PC5020 main control.
- Wire the zones according to the description found in the control panel Instal-
Z1 to Z8
lation Manual.
Enclosures
The PC5108FLR can be installed in the metal enclosures listed below. Tamper protection
switches can be installed on all enclosures, including door opening protection and/or
removal from the mounting position. Doors can be secured using screws or keylock.
•Model PC5003C (removable door) made of 22Ga steel, painted, dimensions:
248mm(L) x 298mm(W) x 76mm(H), weight: 1500g.
•Model PC5003C (hinged door) made of 1.2mm thick steel, painted, dimensions:
248mm(L) x 298mm(W) x 76mm(H), weight: 2500g
•Model Power UC1 made of 18Ga steel, painted, dimensions: 315mm(L) x 319mm(W) x
100mm(H), weight: 3150g.
•Model PC4003C made of 18Ga steel, painted, dimensions: 230mm(L) x 180mm(W) x
75mm(D), weight 1050g.
Jumper Settings
OFF
ON
ON
The PC5108FLR module can be used
J1
J2
J3
to add up to 8 additional hardwired
fast loop response zones to the
PC1616, PC1832, PC1864 or
PC5020 control panel (see Installa-
PC5108
tion Manual for complete installation
instructions).
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8
Z8
Jumpers
The PC5108FLR will operate in a sin-
gle group of eight zones. Refer to the
following jumper settings:
To Add Hardwired Zones to a Control Panel
KEYBUS TO
ADDITIONAL
1. Connect module to the Keybus (with the panel powered down).
EXPANSION
MODULES
2. Set the jumpers on the module.
3. Power up the system.
4. Enter section [902] and wait 1 minute.
5. Enter section [903] to verify that the module is supervised.
6. Define the zones in sections [002]-[004] for PC1616, PC1832, PC1864 or PC5020.
7. Add the zones to the appropriate partition in sections [202]-[265].
LIMITED WARRANTY
Digital Security Controls warrants that for a period of twelve months from the date of pur-
chase, the product shall be free of defects in materials and workmanship under normal use and
that in fulfilment of any breach of such warranty, Digital Security Controls shall, at its option,
repair or replace the defective equipment upon return of the equipment to its factory. This
warranty applies only to defects in parts and workmanship and not to damage incurred in
shipping or handling, or damage due to causes beyond the control of Digital Security Controls
such as lightning, excessive voltage, mechanical shock, water damage, or damage arising out
of abuse, alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any
and all other warranties, whether expressed or implied and of all other obligations or liabilities
on the part of Digital Security Controls. This warranty contains the entire warranty. Digital
Security Controls neither assumes responsibility for, nor authorizes any other person purport-
ing to act on its behalf to modify or to change this warranty, nor to assume for it any other
warranty or liability concerning this product. In no event shall Digital Security Controls be
liable for any direct or indirect or consequential damages, loss of anticipated profits, loss of
time or any other losses incurred by the buyer in connection with the purchase, installation or
operation or failure of this product.
Warning: Digital Security Controls recommends that the entire system be completely
tested on a regular basis. However, despite frequent testing, and due to, but not limited to,
criminal tampering or electrical disruption, it is possible for this product to fail to per-
form as expected.
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security
Controls could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used
properly, in strict accordance with the manufacturer's instructions, may cause interference
to radio and television reception. It has been type tested and found to comply with the limits
for Class B device in accordance with the specifications in Subpart "B" of Part 15 of FCC
Rules, which are designed to provide reasonable protection against such interference in any
residential installation. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause interference to television or radio recep-
tion, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
Expander Zones
Jumpers
Zones Assigned
• Re-orient the receiving antenna
Group A (Zones1-8) J1
J2
J3
• Relocate the alarm control with respect to the receiver
• Move the alarm control away from the receiver
Group B (not used)
• Connect the alarm control into a different outlet so that alarm control and receiver are on
ON ON ON Zones Disabled
different circuits.
OFF ON ON Zones 9-16
If necessary, the user should consult the dealer or an experienced radio/television technician
ON OFF ON Zones 17-24
for additional suggestions. The user may find the following booklet prepared by the FCC
OFF OFF ON Zones 25-32
useful: "How to Identify and Resolve Radio/Television Interference Problems". This book-
let is available from the U.S. Government Printing Office, Washington D.C. 20402, Stock #
ON ON OFF Zones 33-40
004-000-00345-4.
OFF ON OFF Zones 41-48
ON OFF OFF Zones 49-56
OFF OFF OFF Zones 57-64
©2008 Digital Security Controls Toronto, Canada • www.dsc.com
Tech. Support: 1-800-387-3630 (Canada & U.S.), 905-760-3036
Printed in Canada