DSC CFP-102 Manual - Página 2
Procurar online ou descarregar pdf Manual para Painel de controlo DSC CFP-102. DSC CFP-102 2 páginas. Fire alarm control panel calculation for standby battery requirement
Standby Battery
Calculation Chart
All components that draw current from the panel while it is in the 'standby' mode (AC
OFF) must be considered for the standby battery calculation. All components that draw
current while in the 'Alarm' mode must be considered for the alarm battery calculation.
Step 1:
The control panel will always draw the currents as shown in the chart.
Step 2:
Typically the alarm current is calculated assuming only one initiating zone is
in alarm. If it is required that more than one zone be considered, add 60 mA
per zone in the Alarm column. Consult the smoke detector manufacture's
installation sheet to determine the standby current of these devices. Write
that number in the 'current per device' column then multiply that number by
the number of devices on the zone. Repeat for each zone.
Step 3:
Consult the Notification Appliance installation sheet to determine the current
draw for each device connected to the NAC. For each NAC, calculate the total
current in alarm and put that number (mA) in the 'Alarm' column. Note: each
NAC can supply 1.5 Amps max. and the output voltage is 24 volts FWR.
Step 4:
Add up all the current drawn from the AUX+ output in the standby and alarm
mode and put those totals in the 'standby' and 'alarm' columns.
Step 5:
For each module added to the system, multiply the number of modules times
the module's 'standby' and 'alarm' currents and write those totals in the
'alarm' and 'standby' columns.
Step 6:
Add up all the currents in the 'standby' column and the 'Alarm' column.
Step 7:
Convert the 'standby' and 'alarm' currents from mA to Amps. (divide mA by
1000)
Step 8:
Write in the 'standby' time required. (24 or 60 Hr.)
Step 9:
Multiply the 'standby' Amps times the 'standby' time to get the 'standby'
Amp-Hr. required.
Step 10: Write in the 'alarm' time required in hours. (5 min. = .08 Hr.)
Step 11: Multiply the 'alarm' Amps times the 'alarm' time to get the 'alarm' Amp-Hr
required.
Step 12: Add the 'standby' Amp-Hr. to the 'alarm' Amp-Hr. for the total Amp-Hr.
required.
Step 13: Multiply the total Amp-Hr. times 1.20 for the
to support the system for the selected 'standby time and the
required
selected 'alarm' time.
For details on the control panel and modules, see their respective installation docu-
ments.
WARNING: Please refer to the System Instruction manual for information on limita-
tions regarding product use and function and information on the limitations as to
liability of the manufacturer.
© 2001 Digital Security Controls Ltd., Toronto, Canada • www.dsc.com
Technical Help Desk (Canada & US): 1-800-387-3630 • Printed in Canada • 29005851 R001
minimum Amp-Hr. battery