DSC ELECTRONICS DP-M Series Manual do utilizador - Página 2

Procurar online ou descarregar pdf Manual do utilizador para Fonte de alimentação DSC ELECTRONICS DP-M Series. DSC ELECTRONICS DP-M Series 16 páginas. High power laboratorypowersupplies

DP-M Series User's Manual
Version 12.11.2021
1. Connection
Our devices are pre-configured to the power grid chosen with order (if not specified otherwise, our devices are
manufactured for the EU power grid 230V 50Hz / 400V 50Hz). Subsequent adjustment after delivery is not possible.
Connecting the device to an unsuitable power source will void any warranty.
Note: Devices of the DP-M series in the performance class 4.000W - 9.000W can cause a high starting current when
switched on. Therefore, the use of circuit breakers of classes C, D or K is recommended.
Voltage (Recommended)
Voltage (Max.)
Frequency
Circuit breaker minimum requirements
Voltage (Recommended)
Voltage (Max.)
Frequency
Circuit breaker minimum requirements
Voltage (Recommended)
Voltage (Max.)
Frequency
Circuit breaker Minimum requirements
1 Phase / EU Power Grid
1 Phase / American Power Grid
3 Phase / EU Power Grid (TN-S Network)
DSC-Electronics Germany • Georgstraße 36 • 53111 Bonn
DSC-Electronics Germany • Georgstraße 36 • 53111 Bonn
230V ± 10% AC
250V AC
50Hz - 60Hz
The maximum current of the device shall be determined as
follows:
I = (maximum power of the device / 230) + 2
115V ± 10% AC
130V AC
50Hz - 60Hz
The maximum current of the device shall be determined as
follows:
I = (maximum power of the device / 115) + 4
380V - 410V
430V
50Hz
The maximum phase current of the device shall be
determined as follows:
I = ((maximum power of the device / 400) / 1,73) + 2