Programming Instructions
1.
Disconnect power to the UDS1100.
2. Make the connections to the DSX-USB module.
3. Start KB2CW and select Comm Port / Define Port and enter the
port number the DSX-USB is connected to.
4. Caps Lock is OFF, Hold x on the keyboard, power up the unit.
5. After prompt, quickly press Enter for Setup Mode.
6. Type 0 to choose the '0 Server' option.
7. Enter IP Address, pressing Enter after each octet.
8. Type Y to set Gateway IP Address.
9. Enter Gateway IP Address, pressing Enter after each octet.
10. Use Chart to the right to determine Netmask. Enter 8, 16 or 24.
11. Press Enter twice to accept the default <N> for the next two
12. options.
13. Type 1 to choose 'Channel 1' options.
14. Press Enter to choose Baud 9600.
15. Set I/F Mode. RS-232 = 4C. RS-485 = 4D
16. Press Enter to accept Flow Control '00'
17. Enter TX port number from the Comm Port in Database.
18. Connect Mode = CC
19. Datagram Type = 01
Send Broadcast = N
20. Remote IP Address = Comm Server Ip Address.
21. Typically, you press Enter to accept Remote Port <0>.
22. If both ports are defined in the software, they must both be
defined here. Mux requires both ports to be used and possibly
different.
23. Press Enter to accept the remaining defaults.
24. Press 9 to Save and Exit. Connect the unit to the controller.
All connections are made through the DB-25 connector to the controller.
See wiring info below:
Master Controller Communications
RS-232 Terminations
DB-25
2
at UDS1100
Note /// Requires the
UDS1100
"I/F Mode" set to "4C"
Connections
at DSX Panel
TX
1042
3
1043
15 16 17
1044
3
1030 Series
49 50 51
DSX Access Systems, Inc.
3
7
12
RX GND
+12v
4
5
4
5
214-553-6140
Netmask Chart
Class A = 24 (255.0.0.0)
Class B = 16 (255.255.0.0
Class C = 8 (255.255.255.3)
UDS-1100 Connections
To Master Controller
Db25
2
3
7
12
14
15
21
22
RS-485 Terminations
DB-25
14
at UDS1100
Note /// Requires the
UDS1100
"I/F Mode" set to "4D"
Connections
at DSX Panel
RX+ RX- TX+ TX-
1022
49 48 51 50
1021 & 1020
51 52 49 50
1030 Series
55 56 53 54
www.dsxinc.com
Color/Stripe
Panel
Brown
Tx
Red
Rx
Blue
Gnd
Teal
+12V
Brown/Black Rx+
Red/Black
Rx-
Grey/Black
Tx+
White/Black
Tx-
15
21
22
7 12
GND +12v
(10/2023)