Absolute Process Instruments APD 1420 Manual de início rápido - Página 2

Procurar online ou descarregar pdf Manual de início rápido para Sistema de segurança Absolute Process Instruments APD 1420. Absolute Process Instruments APD 1420 2 páginas. Rtd input alarm trips, factory ranged, isolated

Installation and Setup
Precautions
WARNING! All wiring must be performed by a qualified elec-
trician or instrumentation engineer. See diagram for terminal
designations and wiring examples. Consult factory for assis-
tance.
WARNING! Avoid shock hazards! Turn signal input, output,
and power off before connecting or disconnecting wiring, or
removing or installing module.
Précautions
ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de
câblage. Consulter l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal
d'entrée, le signal de sortie et l'alimentation électrique avant
de connecter ou de déconnecter le câblage, ou de retirer ou
d'installer le module.
API maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. See api-usa.com for
latest product information. Consult factory for your specific requirements.
WARNING: This product can expose you to chemicals includ-
ing nickel, which are known to the State of California to cause
cancer or birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
Input
The sensor type and temperature range are factory config-
ured. See the model/serial number label for module infor-
mation, sensor type, temperature range and options. Tem-
perature sensor inputs are connected as shown in the wiring
diagrams below.
Alarm Types
Note that the deadband is symmetrical about the setpoint;
relay trip and reset points will both change if either the set-
point or deadband are changed.
High Alarm (default, H, or HH): The alarm relay changes state
when the temperature exceeds the deadband trip point. The relay
resets when the temperature drops below the deadband reset
point. For a high alarm, the trip point is above the reset point.
Low Alarm (L or LL): The alarm relay changes state when the
temperature goes below the deadband trip point. The relay
resets when the temperature exceeds the deadband reset
point. For a low alarm the trip point is below the reset point.
HT: Latching alarm with push button reset
HP: Latching alarm with power-off reset. Module power must
be turned off to reset alarms
R: Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
Relay Output Terminals
See wiring diagrams below right for connections. APD mod-
ules do not provide power to the relay contacts. Inductive
loads (motors, solenoids, contactors, etc.) will greatly shorten
relay contact life unless an appropriate RC snubber is in-
stalled.
The APD 1400 operates two sets of relays in unison with a
single setpoint. The dual SPDT contact sets are in a Form C
configuration.
The APD 1420 operates two sets of relays independently,
each with its own setpoint. The dual SPDT contact sets are in
a Form C configuration.
Module Power Terminals
Check model/serial number label for module operating volt-
age to make sure it matches available power.
When using DC power, either polarity is acceptable, but
for consistency with similar API products, positive (+) can
be wired to terminal 13 and negative (–) can be wired to
terminal 16.
Mounting To a DIN Rail
Install module vertically on a 35 mm DIN rail in a protective
enclosure away from heat sources. Do not block air flow. Al-
low 1" (25 mm) above and below housing vents for air cir-
culation.
1. Tilt front of module downward and clip the lower mount
with spring clips to the bottom edge of DIN rail.
2. Push front of module upward until upper mount snaps into
place.
A
P
BSOLUTE
ROCESS
Removal From a DIN Rail
1. Push up on the bottom back of the module.
2. Tilt front of module downward to release upper mount
from top edge of DIN rail.
3. The module can now be removed from the DIN rail.
Setup and Calibration
The input range is factory calibrated and does not require
adjustment.
Relay operation is factory configured. See model/serial num-
ber label for relay configurations.
The Setpoint potentiometer allows the operator to adjust the
level at which the alarm is activated. This control is adjustable
from 0 to 100% of the input range.
The Deadband potentiometer allows the alarm trip and reset
window to be adjusted symmetrically about the setpoint from
1 to 100% of the span. This allows the operator to fine tune
the point at which the alarm trips and resets. The deadband
is typically used to prevent chattering of the relays or false
trips when the process signal is unstable or changes rapidly.
To calibrate the alarm section, set the deadband control to the
minimum (counterclockwise). The deadband will be 1.0% of
input span in this case.
Set the signal source to a reference that represents the
desired trip point.
Adjust the setpoint control to the point at which the relay
changes state from a non-alarm to an alarm condition.
If a larger amount of deadband is desired turn the deadband
potentiometer clockwise. The deadband is symmetrical about
the setpoint; both transition points will change as deadband
is increased.
Relay set and reset points will both change if the setpoint or
deadband are changed. Alternately set the setpoint and dead-
band until the desired trip and rest points are set.
Output Test Function
When the front test button is depressed it will drive the relays
to their opposite state. A customer-supplied switch connected
to terminal 4 and 8 can also be used to toggle the relays. When
released, the relays will return to their prior states.
This can be used as a diagnostic aid during initial start-up or
troubleshooting, or as a manual over-ride function. The Test
button also resets the relays on models with the HT option.
Operation
The green LoopTracker
input LED provides a visual indica-
®
tion that a signal is being sensed by the input circuitry of
the module. It also indicates the input signal strength by
changing in intensity as the process changes from minimum
to maximum.
If the LED fails to illuminate, or fails to change in intensity as the
process changes, check the module power or signal input wiring.
Note that it may be difficult to see the LEDs under bright lighting
conditions.
The bi-color alarm LED provides a visual indication of the
alarm status. In all configurations, a green LED indicates
a non-alarm condition and a red LED indicates an alarm
condition.
In the normal mode of operation, the relay coil is energized in
a non-alarm condition and de-energized in an alarm condi-
tion. This will create an alarm condition if the module loses
power. For a normal acting, non-latching configuration, the
alarm will activate when the input signal exceeds the setpoint
(HI alarm) or falls below the setpoint (LO alarm), then will
automatically reset when the alarm condition no longer exists.
For a reverse acting alarm, the relay coil is de-energized in a
non-alarm condition and energized in an alarm condition. The
alarm activates when the input signal exceeds the setpoint (HI
alarm) or falls below the setpoint (LO alarm), then automati-
cally resets when the alarm condition no longer exists.
For models with the latching relay option, it will be necessary
to push the Test button or remove power from the module to
reset the alarm, depending on the type of latching option. The
alarm will only reset if the alarm condition no longer exists.
I
NSTRUMENTS
Relay 1
Relay 2
Input
9 10 11
Power
Test
Deadband
Setpoint
APD 1400
RTD Input to
Single Alarm Trip
Two Wire RTD Input
To maintain full isola-
tion avoid combining
power supplies in
common with input,
output, or unit power.
3-Wire RTD Input
Cu 60/75°C
conductors
14 AWG
max.
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
APD 1400, APD 1420
1 2 3
4
4 and 8
Relay Test
5 6 7
8
Wire terminal torque
0.5Nm to 0.6Nm
(4.4 to 5.3 in-lbs)
To avoid damage
to the module,
do not make any
connections to
unused terminals
To maintain full isola-
tion avoid combining
power supplies in
12
common with input,
13 14
output, or unit power.
15
16
Customer-Supplied
Remote Test Switch
NO C NC
1
2
3
4
NO C NC
5
6
7
8
Relay Wiring APD 1400
Customer-Supplied
Remote Test Switch
NO C NC
RLY 1
1
2
3
4
NO C NC
RLY 2
5
6
7
8
Relay Wiring APD 1420
Deadband 2
Alarm 2
Setpoint 2
Input
Test
Input
Loop
Loop
Tracker
Tracker
Deadband 1
Alarm
Alarm 1
Setpoint 1
APD 1420
RTD Input to
Dual Alarm Trip
9
10
11
2-Wire Input
Jumper 10 & 11
9
10
11
13
14
15
Module Power
AC or DC +
AC or DC –
api-usa.com
12
12
16