Auber TD100 Manual de instruções

Procurar online ou descarregar pdf Manual de instruções para Controlador de temperatura Auber TD100. Auber TD100 3 páginas. Temperature controller

AUBER INSTRUMENTS
Instruction Manual
1. Overview
This temperature controller contains one temperature probe and two
independent outputs. One output is for cooling device such as
refrigerator and the other one is for heating device. It can be used for
applications such as beer fermentation or convert a refrigerator to
kegerator. By using both cooling and heating devices, the refrigerator
can be controlled at specific temperature regardless in hot summer or
cold winter.
This controller is a plug and play controller. No wiring is needed for
the heater or cooler. Both the heating and cooling control modes are
simple on/off control, similar to a mechanical thermostat but with
much higher precision due to adjustable hysteresis band, precise
sensor and digital read out. Anti-short function is provided for cooling
to protect the compressor from being turned on with high pressure
Freon.
Different operation temperature ranges of the two outputs can be set
separately. Once the cooling range is set, the controller program will
automatically limit the heating range to prevent both heating and
cooling from being turned on at the same time.
A digital silicon band gap sensor is used . The advantage is being
much more reliable in moisture environment than thermistor sensor. It
can be immersed over extended period of time. It also has a more
uniform accuracy over an entire specified temperature range.
2. Specification
Temperature Control Range
Temperature Resolution
Temperature Accuracy
Temperature Control Mode
Temperature Control Output
Audio Alarm
Sensor Type
Sensor Size
Sensor Measuring Range
Ambient Temperature
Dimension
Input Power
Sensor Cable Length
Power Cable Length
Warranty
2013.05
TD100 TEMPERATURE CONTROLLER
INSTRUCTION MANUAL
-50~125 °C, -58~257 °F
0.1 °C (between -9.9 ~ 99 °C)
1 °C (between -50 ~ 10 °C, 100~125°C)
0.1 °F (between -9.9~99.9 °F )
1 °F (between -58 ~ 10 °F,100 ~257 °F)
0.5 °C or 0.9 °F
On/Off Control. Heating and Cooling
10A, 120V or 240V AC *
High and Low Limit
Silicon Band Gap Sensor
0.25" OD (6.35 mm) x 1" (25mm) long
-20~125 °C
-20~ 50 °C
91x140x46mm
85 ~242VAC, 50Hz/60Hz
3 ft (1m)
3 ft (1m)
1 Year
Version 1.1
3. Front Panel
Measured
Temperature
Cooling Device
On Indicator
Cooling Device
Socket
Figure 1. Front Panel
4. Setup Flow Chart
When the controller is powered on, it will display the measured
temperature. The controller will keep running according to the saved
setting. If the temperature sensor is shorted, the controller will display
"Err". Please see Figure 2 for the flow chart to set the parameters.
Measured
6 8.9
Temperature
SET
5 sec
AH
Alarm High Limit
SET
Alarm Low Limit
AL
SET
Cooling Differential
CDF
SET
HDF
Heating Differential
SET
Cooling Antishort
AS
SET
Sensor Failure
SFA
Operation
SET
Temperature Offset
OFS
SET
C-F
Temperature Unit
WWW.AUBERINS.COM
Set Key
Up Key
Dn Key, Mute Alarm
Heating device
On Indicator
Heating Device
Socket
SET
Cooling
CSP
Set Point
SET
Heating
HSP
Set Point
SET
Figure 2 Set
Up Flow Chart
SET
6 8.9
P1/3