Auber Instruments SYL-5342P-S Manual de instruções - Página 4

Procurar online ou descarregar pdf Manual de instruções para Controlador de temperatura Auber Instruments SYL-5342P-S. Auber Instruments SYL-5342P-S 10 páginas. Usb ramp and soak pid temperature controller

AUBER INSTRUMENTS
PV
SV
SET
2S
AL1
al1
200
Alar m 1
SET
AL2
al2
10
Alar m 2
SET
pb
Pb
0
Input O ffset
SET
P
p
0
Pr oportional constant
SET
I
i
500
Integral time
SET
d
d
100
Der ivative time
SET
t
t
10
Cycle time
SET
filt
FILT
20
PV input filter
SET
Hy
hy
0.5
Hysteresis Band
SET
dP
dp
1
Decimal point position
SET
OutH
outh
200
Output high limit
SET
outl
OutL
0
Output low limit
SET
Figure 4. Flow chart for system parameter menu
5.3.1. Alarm function & parameters
This controller has two alarm output relays: AL1 relay (terminal 1 & 2) and AL2
relay (terminal 13 & 14). AL1 relay is temperature alarm. AL2 relay is program
ending alarm.
This controller has three alarm parameters: AL1, AL2, ALP.
Parameter AL1: Temperature alarm value for AL1 relay. See ALP definition
below.
Parameter AL2: Duration time for program ending alarm. Unit is per seconds.
Available range is 0s to 200s. AL2 is set as 10s, it means once the ramp soak
program is completed, AL2 relay will be triggered continuously for 10s. Then it
will be dropped off.
ALP: Alarm output definition for AL1 relay. The temperature difference to release
the triggered alarm is 0.5° F (parameter CF = 1) or 0.5° C (parameter CF = 0).
2020.06
At
at
0
Auto Tuning
SET
Lock
lock
0
Configuration Privilege
SET
Sn
sn
k
Input Sensor Type
SET
Op-a
Reserved
1
SET
cf
CF
c
Display Temp Unit
SET
alp
ALP
1
Alar m output definition
SET
Cool
cool
0
System Function Selection
SET
puh
PuH
1300
Display High Limit
SET
PuL
pul
0
Display Low Limit
SET
Addr
addr
1
Communication addr ess
SET
Baud
baud
0
Communication baud
SET
Table 3. ALP Definition
ALP
Alarm Type
Value
0
AL1 is disabled
Absolute high
1
alarm
Absolute low
2
alarm
Derivation high
4
alarm
Derivation low
5
alarm
Band alarm,
PV < SP – AL1 or
7
direct acting (out
of range alarm)
Band alarm,
8
reverse acting (in
range alarm)
Legend:
PV: current reading temperature
AL1: Value of parameter AL1
SP: Set temperature in current step (SV).
5.3.2. Input offset "Pb"
Input offset Pb is used to add an offset value to compensate the sensor error or
simply to shift the reading. For example, if the controller displays 2ºC when probe
is in ice/water mixture, setting Pb = -2, will make the shift the temperature reading
to 0ºC.
5.3.3. Control mode
1) PID control mode
Please note that because this controller uses fuzzy logic enhanced PID control
algorithm, the definition of the control constants (P, I and d) are different than
that of the traditional proportional, integral, and derivative parameters.
(1) Proportional constant "P"
Please note that the P constant is not defined as Proportional Band as in the
traditional model. Its unit is not in degrees. A larger constant results in larger and
quicker action, which is the opposite of the traditional proportional band value. It
also functions in the entire control range rather than a limited band.
(2) Integral time "I"
Integral action is used to eliminate offset. Larger values lead to slower action.
Increase the integral time when temperature fluctuates regularly (system
oscillating). Decrease it if the controller is taking too long to eliminate the
temperature offset. When I = 0, the system becomes a PD controller.
(3) Derivative time "D"
Derivative action can be used to minimize the temperature overshoot by
responding to its rate of change. The larger the number, the faster the action.
2) On/off control mode
It is necessary for inductive loads such as motors, compressors, or solenoid
valves that do not like to take pulsed power. It works like a mechanical thermostat.
When the temperature passes hysteresis band (Hy, see section 5.3.6), the
heater (or cooler) will be turned off. When the temperature drops back to below
the hysteresis band, the heater will turn on again.
To use the on/off mode, set P = 0. Then, set Hy to the desired range based on
control precision requirements. Smaller Hy values result in tighter temperature
control, but also cause the on/off action to occur more frequently.
WWW.AUBERINS.COM
Alarm ON
Alarm OFF
Condition
Condition
PV > AL1
PV < AL1 – 0.5
PV < AL1
PV > AL1 + 0.5
PV > SP + AL1
PV < SP + AL1 – 0.5
PV < SP – AL1
PV > SP – AL1 + 0.5
PV > SP – AL1 + 0.5
and
PV > SP + AL1
PV < SP + AL1 -0.5
PV > SP – AL1
PV < SP – AL1 – 0.5
and
or
PV < SP + AL1
PV > SP + AL1 + 0.5
P4/10