Anywire AnyWireASLINK BL296PB-16F-4A-20 Manual do produto - Página 5

Procurar online ou descarregar pdf Manual do produto para Terminais tácteis Anywire AnyWireASLINK BL296PB-16F-4A-20. Anywire AnyWireASLINK BL296PB-16F-4A-20 17 páginas.

[How to Connect AnyWireASLINK]
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending on the load current.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving simpli ed wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of connections, hybridization with a four-wire (isolated)
terminal, which supports local power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an external power supply.
[System Configuration Example]
Red: DP
AnyWireASLINK
master
Black:
DN
General-purpose
ASLINK lter
power supply lter
*
24V DC
*
Make sure to use a 24V DC
stabilized power supply for
the power supply to be
connected.
*
When complying with the
UL Standard, make sure to
use a 24V DC stabilized
power supply of "NEC
Class 2 Output."
Dedicated at cable
1.25mm
(4-wire)
2
4P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
24V DC *
Black: DN
[Installation Location]
- Locations where this product is not directly subject to vibration or shock
- Locations where this product is not directly exposed to dust
- Locations where this product is not directly exposed to conductors, such as metal chips or spatters
- Locations without condensation
- Locations where the atmosphere is free of corrosive gases, ammable gases, and sulfur
- Locations far from high-voltage or high-current cables
- Locations far from servos, inverters, and other cables and controllers that generate high-frequency noise
Red: DP
2 points
Black: DN
If the load current consumption
is large, a four-wire (isolated)
terminal can be selected.
This terminal can correspond
Red: DP
to I/O of the controller with an
external power supply.
2 points
Black: DN
Red: DP
Black: DN
Black: DN
The branching
2 points
has no limitation.
Red: DP
2 points
Red: DP
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP, DN terminal farthest
from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
-BL296*B16F*4A20 5/17-
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Size of
the transmission
line (DP, DN)
1.25mm
2
0.75mm
2
0.5mm
2
CAUTION
- Refer to Table 1 so that the size and length of the transmission
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the
AnyWireASLINK master unit and each device.
16 points
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the
"total line length."
- Connect the terminator (with polarity) to the DP, DN terminal
farthest from the AnyWireASLINK master unit.
16 points
Black: DN
2 points
Supply current on the transmission line (DP, DN)
Total length:
Total length: Over 50m,
50m or less
no longer than 100m
MAX 2A
MAX 1A
MAX 1.2A
MAX 0.6A
MAX 0.8A
MAX 0.4A
Total length: Over 100m,
no longer than 200m
MAX 0.5A
MAX 0.3A
MAX 0.2A