cashco 135 Manual de instalação, operação e manutenção - Página 2

Procurar online ou descarregar pdf Manual de instalação, operação e manutenção para Acessórios cashco 135. cashco 135 4 páginas. Low temperature shutoff

d. After desired delivery pressure is set, tighten
the lock nut on the pressure adjusting screw.
3. The main regulator (7) will respond to an increase
in demand in less than ten seconds. The pressure
IV. MAINTENANCE
1. The Model 135 thermal probe (5) is shipped from
the factory preset per the customer's order speci-
fications. All maintenance should be performed at
the factory.
WARNING 1
!
SYSTEM UNDER PRESSURE. Relieve all pressure
prior to performing any maintenance on the PTCM.
Failure to do so could result in personal injury.
2. To relieve pressure for removal and replacement
of Model 135 thermal probe (5), shutoff by-pass
valve (8) and isolation block valve (9). Bleed down
pressure through isolation block valve (10). After
2
SECTION IV
Set Screw
Outlet Vent
1/2" (DN15) NPT
Insertion Threads
Figure 1: Model 135
will initially take a small dip and rebuild to setpoint
over this period. Response to a reduction in de-
mand is immediate. An overshoot of 2-3 psi
(.14-.21 Bar) in the customer delivery pressure
can be expected.
all pressure is relieved, close isolation block valve
(10). The by-pass valve (8) can then be reopened
to supply customer with process gas while the
Model 135 thermal probe (5) is removed and
replaced.
3. Emergency temperature adjustments can be per-
formed if mandatory (see Figure 1). Loosen set-
screws on the body to allow adjustments. The
adjustments occur between the control head and
the milled flats on body. The control head is turned
counter-clockwise (CCW) to lower the tempera-
ture setpoint. A clockwise (CW) rotation will raise
the temperature setpoint. Make adjustments in
incremental steps not to exceed five degrees rota-
tion. After desired temperature setpoint is ob-
tained, tighten set screws. NOTE: Allow sufficient
time for temperature to stabilize before checking
temperature setpoint after each adjustment.
Control Head
Body
Body Flat
External Sheath
Invar Rod
IOM-135