Danfoss VLT CDS 302 Manual de resolução de problemas - Página 9
Procurar online ou descarregar pdf Manual de resolução de problemas para Accionamentos DC Danfoss VLT CDS 302. Danfoss VLT CDS 302 18 páginas. Compressor drives
Check List
Figure 5: Check control
cables
Figure 6: Disconnect all
control wiring
Fault Symptoms in the
compressor (motor):
Motor will not run
LCP Stop
Figure 7: LCP stop = OFF key
pressed
Stand by (figure 8)
Trouble shooting
• The first step is to rule out the problem in the control wiring.
• Disconnect all control wiring by unplugging the
control terminal blocks from the control card.
All control wiring should be checked for shorts
or incorrect connections.
• First verify that the unit is properly powered up
and there is no warning or alarm .
• The most common cause of this is either
incorrect control logic or an incorrectly
programmed drive.
The LCP stop message is displayed when the OFF
key has been pressed.
The stand by message is displayed when there is
no start signal at terminal 18.
• If the display stays lit then the problem is in the
control wiring.
• If the display continues to cut out, the fault
can be located in either the LCP itself or on
the Power card.
Such occurrences will result in one or more of the
following status messages being displayed:
The bottom section of the display will also be
flashing when this occurs.
Ensure that a start command is present at
terminal 18.
9
FRCC.PC.036.A2.02