Installation Instructions
1.1.3 Connection to FCP 106 or FCM 106
1.
Connect the LOP as shown in Table 1.2 and
Illustration 1.3.
2.
After completing connections, cut off or isolate
excess wire.
3.
Connect terminal 27 to +24V or set 5-12 Terminal 27
Digital Input to [0] No operation.
Colour of wire
Terminal
White
53
Brown
18
Purple, orange or
19
grey
Green
27
Red
12
Yellow
50
Blue
55
Table 1.2 Wiring to FCP 106 or FCM 106 Terminals
1.1.4 Set-Up
1.
Perform set-up according to Table 1.3.
2.
Use the [+]/[-] keys to set reference.
3.
At power up, the unit is always in stop mode. The set reference is stored during power down. To set up permanent start
mode, connect terminal 12 to terminal 19 and do not connect purple/grey wire to terminal 12. Permanent start mode will
disable the stop function on the LOP.
Function
Default - Dual speed operation
(connect purple or orange wire)
Function 2 - Dual mode
operation
(connect purple or orange wire)
Function 3 - Dual direction
operation (connect grey wire)
Table 1.3 LOP Operation Mode
1)
Set Jog speed in 3-11 Jog Speed [Hz]
2)
When reset is required, set 5-11 Terminal 19 Digital Input to [1] Reset.
2
LOP Connection and Set-up
Function
Reference
Reset
See Table 1.3, under Key I
See Table 1.3, under Key II
+24 V
+10 V
Ground
Settings
No changes to factory setting.
Select desired modes of operation in Setups 1 and 2
Set 0-10 Active Set-up to [9] Multi Set-up
Set 5-13 Terminal 29 Digital Input to [23] Set-up select bit 0
Set 4-10 Motor Speed Direction to [2] Both directions
Set 5-13 Terminal 29 Digital Input to [11] Start reversing
Danfoss A/S © Rev. 2013-12-02 All rights reserved.
Illustration 1.3 LOP Connections to FCP 106 or FCM 106
Key I (Start)
Run on set
reference (+/-)
Run with
Setup 1
Run forward
Key II (Start)
Key (Stop)
1)
2)
Run on 5 Hz
Stop (and reset
jog speed
- if trip)
2)
Run with
Stop (and reset
Setup 2
- if trip)
2)
Run reverse
Stop (and reset
- if trip)
MI03L102