Gain - min. (return temp. limitation - min. influence)
Setting range
-9.9 ... 9.9
Determines how much the flow temperature will be influenced if the return temperature is lower than
the desired 'Limit' (line 4030) (P control).
Influence higher than 0:
The desired flow temperature is increased, when the return temperature gets below the
set limit.
Influence lower than 0:
The desired flow temperature is decreased, when the return temperature gets below the
set limit.
Example
The return limit is active below 50 °C.
The influence is set to -3.0.
The actual return temperature is 2 degrees too low.
Result:
The desired flow temperature is changed by -3.0 x 2 = -6.0 degrees.
Normally, the setting in line 4036 is 0 in district heating systems because a lower return
temperature is acceptable.
Typically, the setting in line 4036 is higher than 0 in boiler systems to avoid a too low return
temperature (see also line 4035).
Intgr. time (time constant for return temp. limitation)
Setting range
OFF / 1 ... 50 s
Controls how fast the return temperature adapts to the desired return temperature (I control).

OFF:

The control function is not influenced by the 'Intgr. time'.
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
14
VI.KT.F2.02
4036
Factory setting
0.0
4037
Factory setting
25 s
© Danfoss 06/2008
DH-SMT/DK
Control param. (control parameters)
Auto tuning
Setting range
ON / OFF
Automatically determines the control parameters for the DHW control. Lines 6184, 6185, 6186 and 6187
do not need to be set, when using auto tuning.
OFF:
Auto tuning is not activated.
ON:
Auto tuning is activated.
The auto tuning function automatically determines the control parameters for DHW
control. Thus you do not need to set the lines 6184 and 6185, as they are automatically
set to the auto tuning function.
Auto tuning is typically used in connection with the installation of the controller, but it
can be activated when needed, e.g. for an extra check of the control parameters.
Before starting the auto tuning, the tapping flow should be adjusted to the relevant
value (see table below).
Recommended tapping load
No. of apartments
Heat transfer (kW)
1-2
30-49
3-9
50-79
10-49
80-149
50-129
150-249
130-210
250-350
If possible, any additional DHW consumption should be avoided during the auto tuning
process. Should the tapping load vary too much, the auto tuning and controller will
return to the default settings.
Auto tuning is activated by setting the function to ON. When the auto tuning is ended,
the function is automatically converted to OFF (default setting). This will be indicated in
the display.
The auto tuning process takes up to 25 minutes.
The motor protection function (line 6174) has to be deactivated during auto tuning.
During auto tuning the circulation pump for tap water must be switched off. This is done
automatically if the pump is controlled by the ECL controller.
Auto tuning is only applicable in connection with valves that are approved for auto tuning,
i.e. the Danfoss types VB 2 and VM 2 with split characteristic.
VI.KT.F2.02
DH-SMT/DK
6000
6173
Factory setting
OFF
Constant tapping load (l / min)
3
(or 1 tap 25% open)
6
(or 1 tap 50% open)
12
(or 1 tap 100% open)
18
(or 1 tap 100% + 1 tap 50% open)
24
(or 2 taps 100% open)