Também para Danfoss ECL Comfort 210: Manual do utilizador (12 páginas), Manual do utilizador (12 páginas), Manual do utilizador (6 páginas), Manual de instalação (4 páginas), Manual de instalação (20 páginas), Manual de instruções (10 páginas), Manual de instalação (7 páginas), Manual de instalação (16 páginas), Manual de instalação (16 páginas), Manual de instalação (16 páginas), Manual de instalação (16 páginas), Manual de instalação (20 páginas), Manual de instalação (16 páginas), Manual de montagem (16 páginas)

Danfoss ECL Comfort 210 Manual de instruções
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
Desired flow T (Desired flow temperature)
Read-out of the desired flow temperature.
- - - :
The floor drying process is not active
Value: The floor drying process is active
Push the dial to:
select / deselect circuit(s) for floor drying
enter / change the graph of the "Functional heating" or "Curing
heating" process
The desired flow temperature can be set at:
X1, X2, X3 and X4 (Functional heating)
X5, X6, X7 and X8 (Curing heating)
Selection of circuit(s) for floor drying:
Examples of graph:
Times for X1, X2, X3 and X4 are the same (0 h)
Desired temperature at X1 is 20 °C
Desired temperature at X2 is 20 °C
Desired temperature at X3 is 20 °C
Desired temperature at X4 is 20 °C
Times for X1, X2, X3 and X4 are different, as shown.
Desired temperature at X1 is 20 °C
Desired temperature at X2 is 50 °C
Desired temperature at X3 is 50 °C
Desired temperature at X4 is 20 °C
8 | © Danfoss | 2017.08
Read-
Circuit number selected
Circuit number not selected
out
Important: The desired flow temperature values, set at X4 and X8 are
used as controlling temperatures:
after the floor drying process, if the application is not to be started
after a power failure
Application with one heating circuit:
If the floor drying process is in operation and the circuit, by accident, is
changed not to be selected, the floor drying process must be restarted.
Application with two or three heating circuits:
If the floor drying process is in operation for two or three circuits and
one of the circuits, by accident, is changed not to be selected, the floor
drying process continues. Just select the circuit in question again.
VI.JM.P2.02