Danfoss AK-RC 111 Manual do utilizador - Página 6

Procurar online ou descarregar pdf Manual do utilizador para Unidade de controlo Danfoss AK-RC 111. Danfoss AK-RC 111 16 páginas. Single phase

Danfoss AK-RC 111 Manual do utilizador
User Guide | Optyma™ control AK-RC 111 single phase

3.0 Technical characteristics

6 | BC309238530328en-000101
Power supply
Voltage
Max power (only electronics)
Rated current (with all loads connected)
Climatic conditions
Working temperature
Storage temperature
Relative ambient humidity
General characteristics
Type of sensors that can be connected
Resolution
Sensor read precision
Read range
Output characteristics
Description
Compressor
Defrost
Fans
Room light
Aux 1 (free voltage contact)
Aux 2 (free voltage contact)
General electrical protection
Dimension characteristics
Dimensions
Insulation and mechanical characteristics
Box protection rating
Box material
Type of insulation
230 V~ ± 10% 50/60 Hz
~ 7 VA
16 A
-5 – 50 °C
-10 – 70 °C
Lower than 90% Hr
NTC 10K 1%
0.1 °C
± 0.5 °C
-45 – 99 °C
Installed relay
Card output characterstics
10 A 250 V~ (AC3) (2HP)
(Relay 30A AC1)
(100000 cicli)
(Relay 30A AC1)
16A 250 V~ (AC1)
(Relay 16A AC1)
2.7 A 250 V~ (AC3)
(Relay 16A AC1)
16 A 250 V~ (AC1)
(Relay 5A AC1)
5(3) A 250 V~
(Relay 5A AC1)
5(3) A 250 V~
Differential magnetothermic circuit breaker 16A
Id=300 mA
(Id=30 mA on request)
Disconnecting power 4.5 kA
18.0 cm x 9.6 cm x 26.3 cm (HxPxL)
IP65
ABS self-extinguishing
Class II
Note
The sum of contemporary
absorptions of these
outputs has not to exceed
16 A
© Danfoss | DCS (vt) | 2020.03