Dungs FRSBV 10010 Series Manual do utilizador - Página 13

Procurar online ou descarregar pdf Manual do utilizador para Controlador Dungs FRSBV 10010 Series. Dungs FRSBV 10010 Series 20 páginas.

Dungs FRSBV 10010 Series Manual do utilizador
9.2 Description of installation
• Carry out the installation according to the
installation layout indicated below.
• Install the safety pressure relief valve in the
direction of flow (arrow / housing).
• Maximum flow velocity in the stabilisation section:
≤ 30 m/s.
• SBV drain pipeline 1" pipe.
Installation layout
1
Item
Designation
1
Input side shut-off valve (e.g. ball valve or shut-off flap)
2
Filter
3
Reducing adapter
4
Input side manometer
5
Controller
6
Stabilisation section
7
SBV
8
Ball valve
9
Output side manometer
10
Pressure tap
11
Pulse tap, SAV
12
Pulse tap, controller
13
Solenoid valve
14
Compensator
13 ... 20
2
4
3
5
• Prevent the accumulation of condensate: Lay the pulse
lines on an incline.
7
9
8
10
12
6
13
11
14