Data sheet
Installation
Disposal
© Danfoss | 2016.11
VFS 2
T
≤150°C for AMV(E) 25 (SU/SD), 35
max
T
≤200°C for other AMV(E)
max
AMV(E) 25(SU/SD)/35
AMV(E) 65x
T
= 150°C ... 200°C AMV(E) 25 (SU/SD), 35
max
Hydraulic connections
Mount according to flow direction as indicated
on valve body.
Valve mounting
Before mounting the valve be sure that the pipes
are clean and free from abrasion. It is essential
that the pipes are lined up squarely with the
valve at each connection and that they are free
from vibrations. Install the motorized control
valves with the actuator in a vertical or horizontal
position but not upside down.
The valve must be dismantled and the elements
sorted into various material groups before
disposal.
≈5
≈5
o
o
Leave sufficient clearance to facilitate the
dismantling of the actuator from the valve body
for maintenance purposes.
The valve must not be installed in an explosive
atmosphere or at an ambient temperature
higher than 50 °C or lower than 2 °C. It must not
be subject to steam jets, water jets or dripping
liquid.
Note that the actuator may be rotated up to 360°
with respect to the valve body by loosening the
retaining fixture. After this operation retighten.