Duomo BX150 Manual - Página 4
Procurar online ou descarregar pdf Manual para Detectores de gás Duomo BX150. Duomo BX150 7 páginas. Gas detection controller
Também para Duomo BX150: Manual (12 páginas)
Configuring The BX150
The BX150 has a DIP switch on the rear panel. Switch 1 is used to control the main alarm delay. Switch 2 is used to
configure the main alarm latching mode. Switch 3 is used to select whether the unit detects toxic or explosive gases.
The BX150 can be configured to provide several modes of operation. The configurable parameters are:
Switch 1 on the DIP switch
Intrinsic safety determines the condition of the main alarm relay and hence
the operation of the gas valve. When it is 'ON' the relay is in a normally open
state. When it is 'OFF' the relay is in a normally closed state. NOTE: This affects
how the gas valve operates and means that you may need to change how it is
wired to the BX150.
Example shows Intrinsic Safety on
Switch 2 on the DIP switch
Main alarm relay actuation method. This can be configured to provide either a
latching or a temporary alarm operation. When the main alarm is actuated in
an alarm condition if the switch is in the 'ON' position the relay will remain in
this position even after the concentration of gas has reduced below the alarm
threshold. If the switch is in the 'OFF' position the main alarm relay will actuate
for 60 seconds and then if the level of gas has dropped will return to the volt-
free main alarm relay to the running condition. The indication on the panel
fascia and the audible alarm will still indicate main alarm. This mode of
operation is used when using manual reset gas valves and battery back-up
systems for extending standby battery life.
Example shows detector configured for a latching main alarm
Main alarm switch in 'OFF' position
Gas Sensed
Main Alarm relay
Reset Pressed
Switch 3 on the DIP switch
Type of gas to be sensed. These are GAS or CO. The symbols on the front fascia
of the detector are EN standard symbols and refer to any explosive or toxic
gas. If toxic gas, e.g. carbon monoxide is to be sensed on a given zone move
the switch to the OFF position. If explosive, e.g. natural gas, LPG, hydrogen etc.
move the switch to the ON position.
Example shows explosive gas setting