Timed Power-Off Configuration
The Trio Labstart can be programmed, during initial
commissioning, to turn off automatically. The ON period
can be set in 1 hour increments up to 12 hours. When
this period has elapsed the Trio Labstart will
automatically turn itself off. This means that the manual
reset test must be completed before the gas and other
services are safely re-introduced to the laboratory.
1.Trio LabStart in a run condition with all outputs active.
2. Hold keys 3, 4 and 9 at the same time for 5 seconds.
Press the Enter key ( ).
3. Select the number of hours required as ON TIME. Press
the Enter key ( ).
Wiring Diagrams
TRIO GAS SAFESTART KS23
AUTOMATIC CONTROL
INPUTS 24V dc 10mA MAX.
OUTPUTS
3A MAX 250 Vac
PF - 100%
VOLT FREE
STATUS RELAYS
A Typical electrical connection for a science laboratory.The Labstart can be used to safely start Gas, Water and Power (Fig. 2)
w: www.duomo.co.uk
INPUT TERMINAL PLUG
GND
OUTPUT TERMINAL PLUG
RUN
FAIL
POWER
-
4. The selected time will flash once in red and the Trio
will return to normal run display.
5. After the selected time has elapsed the Trio will
automatically shut off.
6. This time will be the default 'ON TIME' until the above
procedure is used to change it.
NOTE: By default this function is not set. Therefore the
unit will not auto power-off until you configure it to do
so. To revert back to the default at any time, folllow the
instructions and select '0' at step3.
(EMERGENCY STOPS, FIRE ALARM ETC.)
E
E
Ph
N
1
2
3
4
5
6
WATER VALVE
L
7
N
8
L
9
N
10
L
11
12
13
14
15
16
17
18
-
t: 01905 797989
EXTERNAL LIMITS
Ph
230V ac POWER SUPPLY
N
P
2
3
(IF FITTED)
G621 WEEP BYPASS
ASSEMBLY
1
N
4
-
f: 01905 774296
GAS - PRESSURE
SWITCH
GAS - WEEP
VALVE
GAS - MAIN
VALVE
|
© Duomo (UK) Ltd. 2007