DANLERS CZ CEFL 10VDC Notas de instalação
Procurar online ou descarregar pdf Notas de instalação para Interruptor DANLERS CZ CEFL 10VDC. DANLERS CZ CEFL 10VDC 2 páginas. Controlzapp ceiling flush mounted switches
Variants
DANLERS design and manufacture other ControlZAPP Ceiling Flush Mounted variants,
coded by the following order codes:
CZ CEFL VF
Suitable for mains switching, Volt Free contacts
CZ CEFL 10VDC
Suitable for 1-10VDC ballasts
CZ CEFL 10VDCVF
Suitable for 1-10VDC ballasts, Volt Free contacts
CZ CEFL DALI
Suitable for DALI ballasts
CZ CEFL DALIVF
Suitable for DALI ballasts, Volt Free contacts.
Troubleshooting
The load will not switch on:
• The LUX setting as specified by the ControlZAPP App is set too low and is
inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the control
unit to the DOWN position.
The load switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the CZ CEFL control away from heater.
• Please contact DANLERS for further technical support.
Precautions and Warranty
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected]
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
08/09/16
ControlZAPP Ceiling flush mounted switches
CZ CEFL
ControlZAPP ceiling flush mounted multi functional devices can be flush mounted
into suspended and plasterboard ceilings (diagram A).
ControlZAPP devices incorporate a passive infra-red quad sensor to detect
movement of a warm body within their detection zone (diagram B) and a photocell
to monitor the ambient light level.
ALL adjustments are made via a freely downloadable ControlZAPP App
available from the DANLERS website.
If CZ CEFL is set as PIR with LUX input, upon detecting movement, if the ambient
light is dark enough, the ControlZAPP device will turn the load ON. The ambient
threshold can be set to between approximately 30 lux to 1000 lux and infinite lux
(photocell inactive) via the 'Respond to Daylight' settings on the ControlZAPP App.
If no more movement is detected within a pre-selected time as determined by the
ControlZAPP App, then the ControlZAPP device will turn the load off. This 'Time
Off Timeout' or time lag can be set via the ControlZAPP App adjuster between
10sec and 23hrs 59min 59sec.
Loading
CZ CEFL is suitable for mains switching or DALI switching only.
CZ CEFL can switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) fluorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
Start-up mode and Default settings
When the CZ CEFL is powered up, it will take 1 minute for the circuitry to stabilise
(detection LED flashing) and ensure the output is off, the ControlZAPP device will
then enter its Default Operating Mode.
Please Note: When in the Default Operating Mode the CZ CEFL is set up as an
occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell disabled.
INS004 CZ CEFL
Installation notes