Dantherm Cooling PS023017Y Manual de informações do produto - Página 4

Procurar online ou descarregar pdf Manual de informações do produto para Equipamento industrial Dantherm Cooling PS023017Y. Dantherm Cooling PS023017Y 14 páginas.

Dantherm Cooling PS023017Y Manual de informações do produto
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual

3. MODEL IDENTIFICATION

Model numbering format
3.1.
Pinnacle
S = Standard
X = Custom (further nomenclature invalid)
Nominal Height
018 = 18"
023 = 23"
035 = 35"
060 = 60"
Capacity
017 = 17 W/ºF
022 = 22 W/ºF
026 = 26 W/ºF
035 = 35 W/ºF
045 = 45 W/ºF
055 = 55 W/ºF
100 = 100 W/ºF
Voltage:
A = 115 volt / single phase
B = 230 volt / single phase
Y = 24 VDC
Z = 48 VDC

Options:

-GR
-L
-M
-PXX
-S
-T1
4. OPTIONS
Speed Control (-S)
4.1.
The controller is designed to slow down the speed of the internal and external fans at lower
temperatures to reduce noise and energy consumption. It will also supply either a normally closed
(NC) or normally open (NO) alarm signal for fan fault, sensor fault, or high temperature.
Thermostat Control (-T1)
4.2.
A snap disc thermostat controls the operation of the external loop fan. A temperature rise above
80F will cause the fan to be turned on, a temperature decrease below 60F will cause the fan to be
turned off; between the range of 60F-80F the fan will be operating based on the pervious
environmental condition experienced.
HexFlow Pinnacle Series Product Information Manual
= Additional Environmental Protection
= External Plug
= Stainless Steel Cover
= Non Standard Paint Color
= Speed Controller
= External Fan Thermostat
P S 035 035 Z – T1
Page 4 of 14