Belimo ZoneTight CQKB24-SR-LR Instruções de instalação - Página 4

Procurar online ou descarregar pdf Instruções de instalação para Unidade de controlo Belimo ZoneTight CQKB24-SR-LR. Belimo ZoneTight CQKB24-SR-LR 4 páginas.

Belimo ZoneTight CQKB24-SR-LR Instruções de instalação
Wiring Diagrams
INSTALLATION NOTES
A
Actuators with appliance cables are numbered.
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.
Actuators may also be powered by 24 VDC.
Only connect common to negative (-) leg of control circuits.
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
Actuators with plenum cable do not have numbers; use color codes
instead.
Meets cULus requirements without the need of an electrical ground
connection.
WARNING! LIVE ELECTRICAL COMPONENTS!
!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
800-543-9038 USA
Modulating, Electronic Fail-Safe, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal
Line
Volts
Control Signal
On/Off 110 to 230 VAC
866-805-7089 CANADA
500
VDC/mA
2 VDC
Open
10 VDC
Close
Fail Position
0%
203-791-8396 LATIN AMERICA / CARIBBEAN
CQKB24-SR-LR
2
3
5
7
18
Blk
Common
Red
+ Hot
Wht
Y
Input, 2 to 10V
1
Close