Belimo FS Series Substituição - Página 17

Procurar online ou descarregar pdf Substituição para Motor Belimo FS Series. Belimo FS Series 19 páginas. Replacement of multiproducts motors
Também para Belimo FS Series: Manual de instruções (20 páginas), Folha de instruções (18 páginas)

Belimo FS Series Substituição

Wiring

There are three wiring schemes that describe all applications. While the geometry of the wire runs
may vary, the connections are straightforward.
Regardless of the wiring routes used, this drawing shows the wiring necessary for a UL555S
damper and actuator. Use it as a basis for any of the other wiring schematics. Note that the alarm
connections are not touched when replacing an actuator. This is a major concern for Fire
Marshals.
Honeywell with actuator wiring compartment used for junctions.
If necessary add a chase nipple and junction box as shown above right for wiring connections.
Air Balance Honeywell ML&MS Types to Belimo FSxx
TYPICAL FIRE - SMOKE COMBINATION DAMPER WIRING
Electric thermal disc
Smoke Detector or Relay from area
smoke detection system
HOT
120 or
24 VAC
To alarm
system
Honeywell Wiring
165F
Thermodisc
Green
Ground
Internal to
motor
Com Hot
TYPICAL SENSOR
TEMPERATURES
165°F
N or
COM
BELIMO
FSxx
ACTUATOR
Belimo Mechanical
165 F
Thermodisc
Anti-
rotation
FSLF
strap
FSNF
½" threaded
connector
Chase nipple
Existing flex connector and
incoming power wires
March 2018
2x 4 box and
blank cover
17