Belimo FSNF120 Series Manual de substituição - Página 17

Procurar online ou descarregar pdf Manual de substituição para Motor Belimo FSNF120 Series. Belimo FSNF120 Series 19 páginas. Replacement of safe-air honeywell ml & ms motors

Belimo FSNF120 Series Manual de substituição

Wiring

This is the most common wiring method used.
Regardless of the wiring routes used, this drawing shows the wiring necessary for a
UL555S damper and actuator. Use it as a basis for any of the other wiring schematics.
Note that the alarm connections are not touched when replacing an actuator. This is a
major concern for Fire Marshals.
Fusible link DAMPER ACTUATOR WIRING
In some rare cases fusible links
may have been used. In those
cases the wiring for the actuator
will be similar to this.
Note that where any fire alarm wiring is touched, the
Safe-Air Honeywell ML & MS Motors with Belimo FSNF120 Series
TYPICAL FIRE - SMOKE COMBINATION DAMPER WIRING
Electric thermal disc
Smoke Detector or Relay from area
smoke detection system
HOT
120 or
24 VAC
To alarm
system
Smoke Detector or Relay from area
smoke detection system
HOT
120 or
24 VAC
fire department must be informed.
TYPICAL SENSOR
TEMPERATURES
165°F
BELIMO
FSxx
ACTUATOR
BELIMO
FSxx
ACTUATOR
WARNING!
N or
COM
N or
COM
March 2018
17