BACnet object description
Object Name
Object Type / Instance
MIN_STPT_[n]
Analog Value
MAX_STPT_[n]
Analog Value
NOM_FLOW_[n]
Analog Value

Connecting the PC-Tool for parameterisation of the MP/MFT(2) actuators

www.belimo.com
Belimo Gateway MP to BACnet MS/TP
(continued)
Description
[n*100+1]
Minimum limit (position or flow) in %
Attention: Changing the limit may result in
malfunction of the device.
[n*100+2]
Maximum limit (position or flow) in %
Attention: Changing the limit may result in
malfunction of the device.
[n*100+3]
Nominal volumetric flow (or pressure)
The unit depends on the node type:
[m3/h] for VAV controllers
[Pa] for VAV controller in STP mode
[l/min] for EPIV units
The MP network can be scanned, actuators can be addressed and actuator-specific parameters
(e.g. running time) can be readily adjusted with the Belimo PC-Tool.
The PC -Tool can be accessed directly on the MP-Bus via the RJ12 socket of the
UK24BACMOD. The Gateway recognises the connected PC-Tool automatically and stops
communications with the MP drives.
Belimo
PC-Tool
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes
Values
Default
0...100
-
20...100
-
0...65535
-