WALL SUPPORT HEAVY DUTY (WSHD)
Used for supporting the vent in vertical runs and to provide a
fixed point for thermal expansion consideration. It can
maintain a clearance from the outer wall of the vent from 2-1/2"
to 10".
Figure 49: Wall Support Heavy Duty
WALL GUIDE HEAVY DUTY (WGHD)
Used for guiding in vertical installation attached to the wall. It
can maintain a clearance to the outer wall of the vent from 2-
1/2" to 10".
Figure 50: Wall Guide Heavy Duty
FLOOR GUIDE HEAVY DUTY (FGHD)
Used for guiding in vertical installation when passing through a
floor or roof. Must not be in contact with combustible material.
Figure 51: Floor Guide Heavy Duty
CIXPRO SERIES FOR GREASE DUCT UL1978 SUBMITTAL RECORD
SECTION G – PENETRATION ROOF /
WALL
A chimney that must penetrate through a floor, roof or wall
made of COMBUSTIBLE materials, must use a Roof Thimble
(RT) or a Wall Thimble (WT). The minimum air space
clearance between the outer wall of the chimney and the
combustible material of the roof / floor / wall listed in the Table
1 must always be respected when using a Roof Thimble (RT)
or a Wall Thimble (WT).
Figure 52: Roof Thimble
2-HOUR FIRESTOP
FIRESTOP KIT (TPFK) DIS3Z ONLY
Used to maintain the fire resistance rating of a floor or a wall
when the grease duct DIS3Z is penetrating a 2-hour fire-rated
floor or wall (UL System No. C-AJ-7160). One kit required for
a floor penetration and two kits required for a wall penetration.
Diameter of penetration is outer casing + 2" (Ø ID + 8"). Must
use the firestop caulking S-TPFS (Spec Seal Triple S
Intumescent Firestop Sealant – SSS100). Refer to Table 2
Figure 54: Through Penetration Firestop
SECTION H – FLASHING / STORM
COLLAR
FLASHING (F)
Used in conjunction with storm collar (included) for
weatherization at the roof.
Figure 55: Flashing
REV: 0
AUGUST 2017
Figure 53: Wall Thimble
THROUGH PENETRATION