CHIMNEY INSTALLATION (continued)
5. Firestop spacers are required at each point
where the chimney penetrates a floor or ceil-
ing joist space. Their purpose is two-fold:
they establish and maintain the required
clearance between the chimney and combus-
tible materials, and they also provide com-
plete separation from one floor space to an-
other floor or attic space as required by most
codes. When penetrating a floor or ceiling at
an angle, the appropriate approved firestop
should be used.
When the double wall pipe passes through a framed opening into an attic space, the firestop must be place
in the attic floor. FIG 8a
When the double wall pipe passes through a framed opening into living space above, the firestop must be
placed onto the ceiling from below. FIG 8b
6. Now you are ready to install the termination cap, and storm collar. First install the storm collar around the
exterior of the flue section extending above the roof flashing. Tighten and slide down over the top of the
roof flashing, secure and seal. Install the termination cap as per manufacturer's instructions. See FIG 8.
10-FOOT RULE
All chimney terminations must
extend a minimum of 3' above
the highest point where it
passes through the roof and
must be at least 2' above the
peak of the roof if within a
horizontal distance of 10' from
the peak. See FIG 9.
WARNING: INSTALL ONLY THE TERMINATIONS OUTLINED IN THESE INSTRUCTIONS. A SERIOUS FIRE HAZARD COULD
EXIST IF USING NON-LISTED TERMINATIONS. THIS CHIMNEY SYSTEM IS NOT INTENDED FOR WALL TERMINATION
COMBUSTION AIR SYSTEM INSTALLATION
An outside combustion air kit is required to be installed for Gas Con-
versions, and is recommended for wood burning. Your local codes
1. Connect the side-mount air manifold to the side of the firebox
using supplied screws (FIG 10).
2. Cut a hole and mount the 4" dryer vent on the exterior wall or on
the side of the roof mounted chase as shown in FIG 11.
FIG 8a.
FIG 9. ten foot rule
13
Firestop Installation
FIG 10. side mount air manifold
FIG 8b.