AEZ GCM02 Manual - Página 8
Procurar online ou descarregar pdf Manual para Painel de controlo AEZ GCM02. AEZ GCM02 12 páginas. Automatic microprocessor control panel for stand-by generator
This block diagram indicates the status of the system which powers the
utility.
The trestle illustrates the public mains. The lit LED indicates that the
three phases are within the fixed parameters and vice versa when it is
switched off.
The two CG and CR led indicate which contact maker is closed to power
the utility.
The TRIP led indicates that the differential protection intervention. If it
flashes, it means that there is a leak higher 50% higher than the fixed
parameter. The led on the generator indicates that the generator is
running.
The led on the motor indicates the alarm status of the generator.
Battery charger and battery.
The led indicate that the battery charger is powered and that
the MO2 module is powered by the battery.
The WAIT/PROG led indicates that the micro-controller is
processing. When it stops flashing the processing result will
be obtained; for example, when the led on the mains trestle
is on, it means that the mains has returned within the normal
limits. However the generator CG only switches back to the
mains CR following a settling delay. The WAIT/PROG led
flashes during this delay phase.
The M02 module is equipped with automatic control of the
fuel re-fuelling pump. When it is running the led is on and
the push button is used to its manual control .
Motor starting push button. It is enabled only when the
programming switch is set on 5 MANUAL START. The
control is direct; release the push button once the motor is
running and the led indicates star up in process.
Stop push button that is always enabled. It has to be
pressed until the complete stop of the motor. The led
indicates the motor stop in process.
FILE
VER
LAST ISSUE
LANG.
PAGE
GCM02-M-USO-INGLESE.doc
SDG/02
18/11/2005
ENG
Page 8 of 12