1.2 SUBJECT OF TECHNICAL PRODUCT DOCUMENTATION

The subject of this technical product documentation is application, design and installation of level switches.

1.3 APPLICATION, LEGAL DESIGNATIONS

Level switches are designed for double-position signalling of fluid minimum and maximum.
Designation according to Polish Classification of Products and Services (PKWiU): 26.51.70.0
Designation according to Systematic List of Products (SWW): -0918-132.

1.4 DESIGN AND OPERATION PRINCIPLE

Level switches consists of two main groups, separated with diamagnetic partition:
relay group, being the converting device part, unified for all types.
In the body there is intermediate magnet, directed with equal pole to the float magnet, and the
miniature connector, supplying electric impulses, resulting from magnet lever arm action, to the
connector contacts switching button. To the connector terminals external cables are connected,
guided though the cable gland.
float group, being the level switch sensor group. Depending on level switch application, the float
group is different for each type, and float may look like cylinder with semicircular bowls or ball.
Constant magnet is connected directly or through the lever system to the float, which is directed with the
equal pole to the intermediate magnet of relay group. Float group magnet is protected by housing.
Level switch is activated by the fluid, through the float buoyant force. Fluid level changes cause float
group tilting, which through the magnetic coupling are transferred to the intermediate magnet, which lever
arm closes or opens miniature connector contact. The level switch operation principle is shown by the
following electric diagram. For the minimum level terminals NC-NC are shortened. When level rises,
terminals NC-NC remain shortened until reaching the maximum level. Then the snap switching takes place,
i.e. opening of terminals NC-NC and shorting of terminals NO-NO, which remain shorted until reaching
minimum level by the float.