 Battery Test Mode
In this mode, the UPS will stop the AC/DC section and discharge the battery
while mains input is normal. If the controller found the battery is error, it will
transfer back to line mode immediately, and warning by display to see whether
the battery needs to be replaced. The battery test mode could be trigged in line
mode by pressing the button or by the communication command.
The LCD display in battery test mode is same as the battery mode, The "TEST"
string indicates the UPS is working in the battery test mode.
 ECO Mode
It is also called high efficiency mode. In ECO mode, on LCD display, the mode
sting is "ECO".
After the UPS is turned on, the power used by the load is supplied from the utility
power via internal filter while the utility power is in normal range, so the high
efficiency could be gained in the ECO mode. Once the mains is loss or abnormal,
the UPS would transfer to battery mode and the load is supplied continuously by
the battery.
1) It could be enabled through the LCD setting or the software (WinPower).
2) It is attention that the transfer time of UPS output from ECO mode to battery
mode is less than 10ms. It is suggested to take account of applications for some
sensitive load.
15
 EPO (Emergency Power Off)
It is also called RPO (Remote Power Off). Turn off the EPO switch could occur
RPO .On LCD display, the mode string is "EPO".
It is a special status in which the UPS would shut the output off and alarm. The
UPS could not be turned off by pressing OFF-Button on the panel, only after
releasing EPO status by connecting the EPO switch.
 Converter Mode
CVCF (Constant Voltage Constant Frequency) which is also called converter
mode, the UPS would free run with fixed output frequency (50Hz or 60Hz) in
converter mode. Once the mains is loss or abnormal, the UPS would transfer to
battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (WinPower).
2) The load should be derating to 60% in converter mode.
 Fault Mode
If the UPS generates some internal failure and have to stop its inverter, it will go
into fault mode and alarm by display and buzzer.
In fault mode, the loads have the risk of power loss because the output will come
from the bypass after UPS fault.
In fault mode such as BUS fault etc., the corresponding fault string would be
shown to indicate the operating mode of the UPS. For example "SHOR" would
be shown when the load or the UPS output is short. The LCD display is shown in
the following diagram.