CONTROLLER user manual

Ethernet (option)

Interface to built-in dual port Ethernet switch (future expansion port for IP connectivity).

Device ID

The Controller is equipped with a rotary switch that determines the Device ID (or device address) in the
network. Make sure that the Device ID set on the rotary switch complies with the ID defined in the
configuration settings for this device.
Wrong ID setting will trigger a system fault because of a configuration error.

Micro SD card

The Controller is supplied with a pre-installed micro SD memory card. The memory card contains a
complete system configuration file, including audio messages.
The configuration file is prepared in the 4EVAC Manager – a Windows GUI application. More information
about creating configuration settings can be found in the 4EVAC Manager User Manual.
The memory card is under constant surveillance, as well as its contents. When the memory card is removed,
damaged or its contents are corrupted, the Controller will report a system fault. During a system fault,
caused by a memory error, it enters a safe state where the system stops all functions and requires a reboot.
This state can be reset only by a manual device reset.

CAL button

Firmware version 5.2 and up: This button is not in use (AMP LINK is set up during system reboot, based on
configuration settings)
Firmware version below 5.2: Press this button in order to calibrate the AMP LINK bus. Once calibrated, the
DCA2.500 amplifiers on the AMP LINK will communicate with the controller, exchanging information about
the power supply and amplifier status.

RESET button

Press to trigger a hard reset of the Controller (different from the RESET button on the front panel – soft
reset). This button will trigger a hardware reset of the local Controller only.

GPO

8 x general purpose output (open collector) with common ground.
GPOs are programmable in the configuration settings. The GPO can be linked to any system events to
follow system events and various zone states.
NOTE: Each output can accept max. 110mA and max. 24V open circuit voltage.