Data Aire dap4 touch Manual de Protocolo - Página 7

Procurar online ou descarregar pdf Manual de Protocolo para Unidade de controlo Data Aire dap4 touch. Data Aire dap4 touch 13 páginas. Modbus tcp/ip protocol integration
Também para Data Aire dap4 touch: Manual de início rápido (9 páginas), Manual do utilizador (8 páginas), Instruções de instalação (2 páginas)

Data Aire dap4 touch Manual de Protocolo
Point 
Index 
32
Temperature deadband for heating in economizer mode*
33
Amount temp must change for each stage of heat/cool*
34
Dewpoint setpoint for economizer*
35
deadband of dewpoint for economizer*
36
Lower limit of dewpoint for economizer*
37
deadband of low dewpoint for economizer*
38
deadband of enthalpy for economizer*
39
Offset for Outside Air Temperature probe*
40
Temperature of the outside air*
41
Dew point of outside air*
42
Dew point of return air*
43
Setpoint for fan modulation by return or rack temperature*
44
Amount from setpoint before fan starts ramping up*
45
The highest of the rack temp sensors connected to this unit*
46
The highest rack temp of all units in this zone*
47
Value of rack temperature sensor #1*
48
Value of rack temperature sensor #2*
49
Value of rack temperature sensor #3*
50
Temperature setpoint of the Zone Master*
1
Lower limit alarm of discharge air temp*
2
Relative humidity displayed as xx%
Cooling Stages On = Cooling stages are currently on – This point applies to
3
DX unit only
4
Number of heat stages running
5
Maximum humidity in last 24hrs
6
Minimum humidity in last 24hrs
Cooling Utilization Over Last Hour -Percentage of cooling is used in the last
7
hour of operation; this point applies to DX unit.
Heating Utilization Over Last Hour -Percentage of heating is used in the
8
last hour of operation
Humidifier Utilization Over Last Hour -Percentage of humidifier is used in
9
the last hour of operation
Compressor 1 Runtime -This point applies to DX unit with one compressor
10
-high
Compressor 1 Runtime -This point applies to DX unit with one compressor
11
-low
Compressor 2 Runtime -This point applies to DX unit with dual compressor
12
- high
Compressor 2 Runtime -This point applies to DX unit with dual compressor
13
- low
14
Heater 1 Runtime - high
15
Heater 1 Runtime - low
16
Current second
 
 
Data Aire's dap4 Modbus TCP/IP
Description 
Document: 600‐000‐961 version 4.0 
Read/
Variable Name 
Write 
R/W
Econ_Ht_Deadband
R/W
Stage_sp
R/W
Dewpoint_Hi_SP
R
Dewpoint_Hi_Dband
R/W
Dewpoint_Lo_SP
R
Dewpoint_Lo_Dband
R
Enthalpy_Deadband
R/W
Ain_offs
R
Outside_Temp
R
Outside_Dewpt
R
Ret_Air_Dewpt
R/W
RA_Fan_Setpoint
R/W
RA_Fan_Deadband
R
Rack_Temp
R
Zone_Rack_Temp
R
Rack_T1
R
Rack_T2
R
Rack_T3
R
Master_Temp_Setpoint
R/W
Disch_Air_Lo_SP
R
Humidity_dis
R
Stages_On
R
Heaters_On
R
Maximum
R
Minumum
R
Comp_duty
R
Heat_duty
R
Hum_duty
R
C1_Hours_H
R
C1_Hours_L
R
C2_Hours_H
R
C2_Hours_L
R
Ht1_Hours_H
R
Ht1_Hours_L
R
CURRENT_SECOND
Data 
Modbus 
Type 
TCP/IP 
A
40033
A
40034
A
40035
A
30036
A
40037
A
30038
A
30039
A
40040
A
30041
A
30042
A
30043
A
40044
A
40045
A
30046
A
30047
A
30048
A
30049
A
30050
A
30051
I
45002
I
35003
I
35004
I
35005
I
35006
I
35007
I
35008
I
35009
I
35010
I
35011
I
35012
I
35013
I
35014
I
35015
I
35016
I
35017