4EVAC IMPACT Manual de referência - Página 4
Procurar online ou descarregar pdf Manual de referência para Sistema de segurança 4EVAC IMPACT. 4EVAC IMPACT 8 páginas. Controller
Também para 4EVAC IMPACT: Manual do utilizador (14 páginas)
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4E-IMPACT reference manual
3. Connection diagram
4. Network cabling
The 4EVAC network features a full duplex RS-422 data link and 24V DC power to remote devices.
If you're building a distributed system using the 4EVAC network, you should make physical links between
devices using the right cables. The cabling should meet the following requirements:
1.
Crossover twisted-pair cable (compatible with Ethernet crossover)
2.
CAT5e or higher for maximum distance of 250m.
3.
Non-CAT / lower than CAT5e: 250m not guaranteed.
Page 4 of 8
pin number
GND
shield
RX+
1
RX-
2
TX+
3
power +
4
power -
5
TX-
6
power +
7
power -
8
xover type A cable
pin number
GND
shield
RX+
1
RX-
2
TX+
3
power +
4
power -
5
TX-
6
power +
7
power -
8
xover type B cable
Author:
pin number
shield
GND
1
RX+
2
RX-
3
TX+
4
power +
5
power -
6
TX-
7
power +
8
power -
pin number
shield
GND
1
RX+
2
RX-
3
TX+
4
power +
5
power -
6
TX-
7
power +
8
power -