AddSecure IRIS-4 Manual de instalação e manutenção rápidas - Página 7
Procurar online ou descarregar pdf Manual de instalação e manutenção rápidas para Terminais tácteis AddSecure IRIS-4. AddSecure IRIS-4 9 páginas.
IRIS-4
2 Series
Quick Installation and
Maintenance Guide
To investigate any faults or to perform checks, the
IRIS-4 2 Series dialler gives engineers the option via
the touch screen, to see the current faults, reflash to
latest software and perform communication path
checks . Engineers will need to touch the screen
to exit the screen saver mode and should now be
presented with the welcome screen . Engineers will
now see the option indicating status and the option
to enter the installer menu . The engineer will now be
able to perform the following checks:
7.1. Confirm Current Status
The IRIS-4 2 Series dialler will indicate "Status – ok"
if the current dialler setup is all working correctly,
and if the status is showing "Status – Trouble" the
dialler has a trouble reported . To view the reported
trouble click on the "Status – Trouble" option then
"View Trouble Report" .
Check the reported system troubles via the "Trouble
report" menu . Please refer to the IRIS-4 2 Series
Series Engineering Manual for more details available
from http://www . a ddsecure . c om .
12
7.2. Check Software Version/Reflash
Enter the 'Installer Menu', which will prompt for
the installer code, check installation documentation
to see what this is set to . Once in go to the settings
menu and then scroll down and select the 'Reflash'
option . On first entry to the reflash option, which
could be during installation or maintenance, the
engineer will be required to change the password as
required for EN50136-2 compliance . Please record the
password on the installation documentation .
Enter the correct reflash password and you will then
have the following options .
The AddSecure Reflash server IP address will already
be setup under the 'Reflash IP Address' but if using
an alternative Reflash IP address then change the IP
address . Once you have the correct reflash IP address
entered press the 'Reflash Now' to connect to the
server and check if there is a later version, and if there
is, it will start to reflash .
The reflash will take up to 15 minutes if via 2/3/4G
and approximately 2 minutes with the Ethernet
connection . Once completed the dialler will reboot
and switch to the new software .
Note: All configurations for the IRIS-4 2 Series
dialler are stored and there is no need to reconfigure.
During the reflash process, do not remove power
until dialler has completed and reset.
7.3. Communication Paths Checks
The engineers can test the communication paths
for both polling and alarm communications using
the 'Test' option in the Main Menu . This will
perform communication path checks for each path
configured .
Please refer to the IRIS-4 2 Series Engineering
Manual for more details available from
http://www . a ddsecure . c om .
7.4. test alarm Panel alarms and
Communication to Monitoring Centre
Depending on the Monitoring Centre engineers will
now be required to perform alarm test and possibly
other tests to the Monitoring Centre . Before the engi-
neer leaves site get confirmation from the Monitoring
Centre that all is working correctly .
7.5. touch Screen Calibration
The IRIS-4 2 Series dialler allows Engineers to recal-
ibrate the touch screen if required . To perform this
you have two options as detailed below:
• On initial power on: 'Touch Calibration' box in
the top part of the screen for a few seconds .
• In the Installer Menu > Settings > Display >
Touch Calibration .
Press the 'Touch Calibration' box and follow the
on screen prompts to calibrate the screen, as shown
below:
13