Duro Dyne 35234 Manual de instruções de instalação - Página 7

Procurar online ou descarregar pdf Manual de instruções de instalação para Sistemas de controlo Duro Dyne 35234. Duro Dyne 35234 16 páginas. Zone control system

Wiring diagram for a spring return damper that is normally
open with no power (spring open).
Wiring an HVAC System
the panel can be used with a wide variety of HVAC systems.
Some of the more common configurations follow:
PLEASE NOTE: THE RED4 PANEL MuST
BE POWERED BY AN INDEPENDENT LOW
VOLTAGE POWER SuPPLY AND NOT BY THE
EQuIPMENT LOW VOLTAGE POWER SuPPLY.
FIRST STAGE
Y1
COOLING
Y2
SECOND STAGE
COOLING
C
COMMON
FIRST STAGE
W1
HEATING
SECOND STAGE
W2
HEATING
G
FAN
Y
FAN SPEED
R
LINE
24VAC
VOLTAGE
C
MULTI STAGE
GAS/ELECTRIC SYSTEM
*NOTE 1: Sometimes Y needs to be wired to the
furnace for fan speed.
FIRST STAGE
Y1
COOLING
Y2
SECOND STAGE
COOLING
C
COMMON
G
FAN
R
LINE
24VAC
VOLTAGE
C
OIL BURNER
CIRCULATOR RELAY OR
HOT WATER VALVE
DuroZone
RED4 - InStALLAtIOn InStRUCtIOnS PAGE 7
RED4 InstrManual-7-1-10.indd 7
HEAT PUMP
24VAC
FIRST STAGE
SECOND STAGE
REVERSING VALVE
COOLING
DEFROST
AIR HANDLER
ELECTRIC
STRIP HEAT
FAN
LINE
VOLTAGE
RED4 Panel
Y2
G
W2/E
Y1
W1/B
O
RH
Heat PumP
RC
24VAC
RH-RC
JUMPER
FIRST STAGE
SECOND STAGE
REVERSING VALVE
COOLING
DEFROST
FIRST STAGE
SECOND STAGE
FAN
RED4 Panel
LINE
Y2
VOLTAGE
G
W2/E
Y1
W1/B
O
RH
*NOTE 1: Sometimes Y needs to be wired to the
RC
furnace for fan speed.
RH-RC
JUMPER
R
C
Y1
Y2
O
W
W
G
R
24VAC
C
R
RED4 Panel
C
Y2
Y1
Y2
W2/E
O
Y1
W1/B
W
RH
W1
RC
W2
G
Y
R
24VAC
C
RED4 Panel
Y2
G
W2/E
Y1
*
W1/B
O
RH
RC
RH-RC
JUMPER
*Wire the
W1/B to
heat pump
if valve
reverses in
the heat
mode.
G
O
RH-RC
JUMPER
7/9/2010 5:34:49 PM