Elsner 70512 Instalação e ajuste - Página 12

Procurar online ou descarregar pdf Instalação e ajuste para Controlador Elsner 70512. Elsner 70512 20 páginas. Multifunctional actuators

Elsner 70512 Instalação e ajuste
5.

Transfer protocol

5.1. List of all communication objects

Abbreviations:
R
Read
W Write
C
Communication
T
Transfer
No
Text
1
Software version
100
Channel A status automatic
or manual
101
Channel A manual long
term
102
Channel A manual short
term
103
Channel A manual
movement position
104
Channel A manual slat
position
105
Channel A automatic long
term
106
Channel A automatic short
term
107
Channel A automatic
movement position
108
Channel A automatic slat
position
109
Channel A switch from
manual to automatic
110
Channel A automatic
blocking object
111
Channel A current
movement position
112
Channel A current slat
position
113
Channel A status object
114
Channel A - Approach
position memory manually
115
Channel A - Learn object 0
position memory manually
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
10
Function
Flags
Readable
R-C-

Output

R-CT
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Input
RWC-
Output
R-CT
Output
R-CT
Output
R-CT
Input
RWC-
Input
RWC-
Technical changes and errors excepted.
Transfer protocol
Data Point Type
[217.1]
DPT_Version
[1]
1.xxx
[1.8]
DPT_UpDown
[1.8]
DPT_UpDown
[5.1]
DPT_Scaling
[5.1]
DPT_Scaling
[1.8]
DPT_UpDown
[1.8]
DPT_UpDown
[5.1]
DPT_Scaling
[5.1]
DPT_Scaling
[1]
1.xxx
[1.1]
DPT_Switch
[5.1]
DPT_Scaling
[5.1]
DPT_Scaling
[1]
1.xxx
[1.1]
DPT_Switch
[1.1]
DPT_Switch
Size
2 Bytes
1 Bit
1 Bit
1 Bit
1 Byte
1 Byte
1 Bit
1 Bit
1 Byte
1 Byte
1 Bit
1 Bit
1 Byte
1 Byte
1 Bit
1 Bit
1 Bit