Dust Free 19300 Manual de instalação e operação - Página 6

Procurar online ou descarregar pdf Manual de instalação e operação para Equipamento de iluminação Dust Free 19300. Dust Free 19300 13 páginas. Germicidal uv-c ultraviolet light
Também para Dust Free 19300: Manual de instalação e operação (5 páginas)

DUST FREE
LIGHTSTICK
®
REMOTE LAMP INSTALLATION
• Drill a 7/8" knockout into the delta plate
and place gasket (included) around
knockout.
• Insert lamp directly into knockout and
secure the lamp to the delta plate with
two self-drilling screws. (Screws and
rubber washers included.)
• Connect remote lamp extension cord.
Note: A-Coil delta plate installation
does not use lamp bracket.

POWER MODULE INSTALLATION

• With the lamp cordage facing away from
the mounting surface, install the power
module in a suitable location on the side
of the system or within the control panel
of the air handler using the two long
self-drilling screws (included). Do not
overtighten.
• Drill a 7/8" knockout in the outer sheet
metal where the remote lamp extension
cord will be inserted.
• Connect the power module to constant
24VAC power.
• Connect lamp to power module.
Connectors are keyed for proper
alignment.
WARNING
UV Light Hazard.
Can cause serious eye and skin damage.
Do not look at UV-C light. Wear UV-C eye and
skin protection.
NOTICE
Clean lamp prior to installation.
Use a cotton cloth to remove dirt and
fingerprints. Failure to do so could shorten the
lamp's lifespan.
INSTALLATION & OPERATION MANUAL
®
(A-Coil Delta Plate)
Fig. 4. Insert lamp into delta plate
knockout and secure with screws
and washers. Connect remote lamp
extension cord.
(Remote Lamp)
Fig. 5 Secure power module to air
handler or duct with long screws. Do not
overtighten.
NOTICE
Fully Seat Lamp Connector.
Failure to properly seat lamp connector could
result in improper lamp operation and/or
compromise water resistance.
NOTICE
Lamp cleaning not required after
installation.
Reference specifications page for lamp
replacement part number and schedule.
6