2.4. Connection
The Actuator KNX S1R-B4-UP DES is installed in a flush-mounted box. The con-
nection is made using a KNX connector on the KNX data bus.
The applicable provisions and standards for SELV circuits must
be complied with for installation and cabling at the KNX
connection and the inputs!
ATTENTION!
When first switched on. relays may be live!
The bistable relays used in this product can switch themselves on
when subjected to strong vibration, e.g. during transport.
•
First of all connect the bus voltage; this will switch off the
relays. Then switch on the power supply to the
drive.
The physical address is assigned by the KNX software. There is a button with a con-
trol LED for this on the actuator.
2.4.1. Connection examples
230V drive at the output:
N N
L
L
Mains
(230 V)
PE
N
L
1 2 3 N PE
M
230 AC V
Inputs:
B1
-
+
1
2
3 4
5
6
7
8
GND
IN1
GND IN2
GND
IN3
GND
IN4
Aktor
KNX S1R-B4-UP
DES
Nr. 70536
2.5. Notes on mounting and commissioning
Device must not be exposed to water (rain). This could result in the electronic being
damaged. A relative air humidity of 95% must not be exceeded. Avoid bedewing.
After the operating voltage has been applied, the device will enter an initialisation
phase lasting a few seconds. During this phase no information can be received or
sent via the bus.
For KNX devices with safety functions (e.g. wind or rain blocking), a cyclical moni-
toring of the safety objects must be set up. The ideal ratio is 1:3 (example: if the we-
ather station sends a value every 5 minutes, the actuator must be configured for a
monitoring period of 15 minutes).
3.
Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another ad-
dress into the ETS by overwriting the 15.15.255 address or by teaching via the pro-
gramming button.
Actuator KNX S1R-B4-UP DES • Version: 27.05.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Actuator KNX S1R-B4-UP DES
Fig. 2: Output side
1 Connection terminal for drive
Each terminal contact may be loa-
ded with a maximum of 10 A.
Example: Binary contact on input 1
4.
Disposal
After use, the device must be disposed of or recycled in accordance with the legal
regulations. Do not dispose of it with the household waste!