4 Error Messages
Any operational error is indicated by a red LED and accompanied by an audio alarm. Furthermore, the
display indicates an error status message. To remove the status message on the display and return to the
main menu, press
STOP
4.1 Error Message "Excitation current too high"
The Error message "Excitation current too high" is displayed if the excitation current exceeds expected
values. This value is set to 500 mA. The excitation current can be reduced by selecting lower test voltages
from the device menu.
Figure 4-1:
Error message
"Excitation current too high"
Possible reasons for this are that the transformer is drawing too much current. In that case, the test should
be repeated with a lower test voltage. Another reason for an excitation current which is too high is that the
connections are reversed. If there are no connections errors found, there may be a short circuit within the
transformer itself.
4.2 Error Message "Turns ratio too low"
This message is displayed if the turns ratio of the transformer under the test is lower than 0.8. In this case
the user should check whether H and X cables are misplaced (reversed).
Figure 4-2:
Error message
"Turns ratio too low''
4.3 Error Message "Malfunction"
In the case of an internal error, the TRT30C will display the massage "Malfunction". In this case, the
TRT30C device should be restarted.
If the error occurs repeatedly, please contact the DV P
"Manufacturer Contact Information").
Figure 4-3:
Error message
"Malfunction"