Bender LINETRAXX GM420 Manual de início rápido - Página 7
Procurar online ou descarregar pdf Manual de início rápido para Monitor Bender LINETRAXX GM420. Bender LINETRAXX GM420 8 páginas. Loop monitor
Technische Daten
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Bemessungsspannung .......................................................400 V
Bemessungs-Stoßspannung/Verschmutzungsgrad .........4 kV /III
Sichere Trennung (verstärkte Isolierung) zwischen .....................
............................... (A1, A2) - (E/KE) - (11, 12, 14) - (21, 22, 24)
Spannungsprüfung nach IEC 61010-1
(E, KE) - [(A1-A2), (11-12-14)] ........................................3,32 kV
(E, KE) - (21-22-24) ........................................................2,21 kV
(A1- A2) - (11-12-14) - (21-22-24) .................................2,21 kV
Versorgungsspannung
GM420-D-1
Arbeitsbereich U
........................AC 16...72 V / DC 9,6...94 V
S
Frequenzbereich U
......................................... DC, 15...460 Hz
S
GM420-D-2
Arbeitsbereich U
......................................... AC/DC 70...300 V
S
Frequenzbereich U
.......................................... DC, 15...460 Hz
S
Eigenverbrauch .............................................................≤ 3,5 VA
Messkreis
Schleifenwiderstand R
m
R
Messbereich
........................................................ 0...100 Ω
m
I
Messstrom
.............................................................. DC 20 mA
m
U
Messspannung
..................................................... ≤ DC 24 V
m
Fremdspannung U
f
U
Messbereich
....................................................... AC 0...50 V
f
Bemessungsfrequenz
Abschaltung der Messschleife bei
Wiedereinschaltung der Messschleife .............................≤ 10 V
Zulässige Fremdspannung
Zulässige DC-Fremdspannung
ohne Beeinflussung der Messung .............................. DC 0 V
Schaltglieder
Schaltglieder ........................................................2 x 1 Wechsler
Arbeitsweise .............. Ruhestrom/Arbeitsstrom (Arbeitsstrom)*
Elektrische Lebensdauer ............................... 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ........ AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung . ......230 V / 230 V / 24 V / 110 V / 220 V
Bem.betriebsspannung UL. ..200 V / 200 V / 24 V / 110 V / 200 V
Bem.betriebsstrom ........................ 5 A / 3 A / 1 A / 0,2 A / 0,1 A
Minimale Kontaktbelastung
(Referenzangabe des Relais-Herstellers)................10 mA/5 V DC
( )* = Werkseinstellung
Bestellangaben
Montageclip für Schraubmontage
(1 Stück je Gerät, Zubehör) ........................................B98060008
f
........................................ 42...460 Hz
n
U
.............................. ≥ 12 V
f
U
.........................................≤ 440 V
f
Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
......................................................400 V
Rated insulation voltage
Overvoltage category/ pollution degree
Protective separation (reinforced insulation) between ................
............................... (A1, A2) - (E/KE) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. to IEC 61010-1
(E, KE) - [(A1-A2), (11-12-14)] ........................................ 3.32 kV
(E, KE) - (21-22-24) ........................................................ 2.21 kV
(A1- A2) - (11-12-14) - (21-22-24) ................................. 2.21 kV
Supply voltage
GM420-D-1
Operating range U
...................... AC 16...72 V / DC 9.6...94 V
S
Frequency range U
........................................... DC, 42...460 Hz
S
GM420-D-2
Operating range U
........................................ AC/DC 70...300 V
S
Frequency range U
............................................... 15...460 Hz
S
Power consumption .......................................................≤ 3.5 VA
Measuring circuit
Loop resistance R
m
R
Measuring range
m
I
Measuring current
m
U
Measuring voltage
Extraneous voltage U
f
U
Measuring range
................................................. AC 0...50 V
f
f
Nominal frequency
Disconnection of the measuring loop
Reclosing of the measuring loop ..................................... ≤ 10 V
Permissible extraneous voltage
Permissible extraneous DC voltage,
without influence on the measurement ......................... DC 0 V
Switching elements
Number of switching elements ............ 2 x 1 changeover contact
Operating principle ...........N/C operation / N/O operation (N/O)*
Electrical endurance .........................10000 switching operations
Contact data acc. to IEC 60947-5-1
Utilisation category ....... AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated op. voltage ................230 V / 230 V / 24 V / 110 V / 220 V
Rated op. voltage UL ............200 V / 200 V / 24 V / 110 V / 200 V
Rated op. current. ........................... 5 A / 3 A / 1 A / 0.2 A / 0.1 A
Minimum contact load
(relay manufacturer's reference) 1 ...........................0 mA/5 V DC
( )* = factory setting
Ordering information
Mounting clip for screw mounting
(1 piece per device, accessories) ............................... B98060008
GM420_D00112_00_Q_DEEN/10.2023
LINETRAXX® GM420
..............................4 kV /III
.................................................. 0...100 Ω
....................................................DC 20 mA
............................................... ≤ DC 24 V
m
............................................ 42...460 Hz
n
U
......................... ≥ 12 V
f
U
................................. ≤ 440 V
f