Great Lakes VRX Manual de instruções de instalação - Página 11

Procurar online ou descarregar pdf Manual de instruções de instalação para Racks & Stands Great Lakes VRX. Great Lakes VRX 12 páginas. Highlander variable depth racks

Great Lakes VRX Manual de instruções de instalação

SAFETY CONSIDERATIONS

WARNING: Improper handling and use of the racks could result in equipment damage, serious
injury, or possible death.
Only trained service personnel should be used to remove the enclosure from the pallet. Also, be
sure you have a sufficient number of service personnel. Do not attempt to move enclosures by
yourself.

LOADING EQUIPMENT

WARNING: Only install equipment after the ER Rack has been properly secured. Do not move the
ER Rack assembly while loaded. To maintain a uniform distribution of the mechanical load in the ER
Rack, load the heaviest equipment first, at the bottom of the ER Rack and load the lighter units at the
top.
Only UL
Listed ITE (Information Technology Equipment) units should be installed inside the rack.
®
Be sure to read and follow all individual manufacturer equipment manuals for safety and installation
instructions.
Proper spacing is required when installing electrical equipment to avoid electrical shock. Maintain
minimum spacing between the accessories and components and the computer enclosure assembly
for safe operation of the equipment when installed in accordance with the National Electric Code
ANSI/NFPA 70-1999.
The ambient temperature operating range for the racks and accessories is +50 to +95° F (+10 to
+35° C). The non-operating temperature is -4 to +140° F (-20 to +60° C).
11