ADELSYSTEM ALL IN ONE CBI Series Manual do operador - Página 10
Procurar online ou descarregar pdf Manual do operador para UPS ADELSYSTEM ALL IN ONE CBI Series. ADELSYSTEM ALL IN ONE CBI Series 12 páginas.
10.2.2 Connection Diagram Size4 CBI280
• RJCONN45: It is a normal RJ45 cable
also provided by ADELSystem. It is possible connect in daisy chain up to 32 devices, max distance
1000m, from the Output AUX2 and Aux3.
• RJUSB280: is cable interface RS485 – USB, max lenght 2m, for the connection to PC
Note: If both, DPY351 and ADELViewsystem, are running in the same network at the same time, The
DPY351 must by set in the Modbus as "Viewmode".
10.2.3 Connection Diagram Size3 CBI500
• DPYCONN500: is a special cable for the connection of CBI Size3 and the other device; max leght
0.5m
• RJ45COUPLER: is e T connection RJ45 for daisy Chain with CBI Size3
• RJCONN45: It is a normal IT cable also provided by ADELSystem. It is possible connect in daisy chain
up to 3 devices, max distance 100m, from the Output AUX2.
• RJUSB500: is cable interface RS485 – USB, max leght 2m, for the connection to PC
10.2.4 Bus Termination (Size 3)
Inside the device are present the following electric diagram for the polarization of the Modbus line:
Fail-safe:
• 560 Ohm (Pull Up) at 5 V
• 560 Ohm (Pull Down) at 0 V
Terminations:
• 120 Ohm (LT) between lines