d. Route AC supply leads throught the top or side hole of housing.
Note: to avoid shadowing secure wires into wire guides located on
the sides of the housing.
4. Make the proper connections (see figure 6):
a. For 120VAC, connect the black wire (120VAC) and white (neutral)
to the building utility.
b. For 277VAC, connect the orange wire (277VAC) and white (neutral)
to the building utility.
CAUTION! Risk of electrical shock. Cap unused wires. In all cases,
use suitable wire nuts rated for the applicable voltage to connect to
wires.
c. Feed wires back into the junction box and secure the canopy to the
crossbar so that the canopy is tight against the wall or ceiling.
5. Snap chevrons to the EXIT panel if required.
6. For self-powered units attach battery connectors togeather.
7. Reinstall the front panel.
Self-Powered Models
For test procedures refer to addendum for self-dianostics and self-testing
option.
Maintenance
None required. If AC supply to the unit is to be disconnected for 2 months
or more, the battery must be disconnected, Self-Powered Models only.
Equipment must be tested regularly in accordance with local codes.
Emergi-Lite
Tel: (888) 552-6467
Insert canopy into housing at 20 degree angle and
twist. Quick snap is now locked firmly.
Caution: Trying to remove the canopy after it is
locked into place may cause damage.
Figure 5
Figure 6
Figure 7
Figure 8
Fax: (800) 316-4515
www.emergi-lite.com
ELX LED Exit Series
1) Manual battery test switch
2) Red LED (indicates normal operation
Note: battery is shipped disconnected
Connect battery before closing unit
07/14 750.1789 Rev. A
2/2