NOTE: THE FOLLOWING WIRING DIAGRAMS HAVE BEEN SIMPLIFIED FOR CLARITY.
FIGURE 2A
WIRING DIAGRAM:
SWITCHED
NORMALLY ON LOAD
Wall Switch
Neutral
(see note 3)
Line 120Vac
120V
Neutral
(see note 3)
Ground
FIGURE 2B
WIRING DIAGRAM:
NORMALLY OFF LOAD
IMPORTANT:
FOR NORMALLY OFF LOADS:
REMOVE THIS JUMPER WIRE.
(see note 3)
Line 120Vac
120V
Neutral
(see note 3)
Ground
Emergi-Lite®
Tel: (888) 552-6467
®
ACTUAL POSITION OF COMPONENTS WILL VARY
Input Wiring
Un-Switched
Primary
Un-Switched
AC Input
Normally ON
Lighting Load
Input Wiring
Un-Switched Line
Neutral
Primary
Un-Switched
AC Input
Normally ON
Lighting Load
Switched or
Triac Dimmer
Device
Neutral
Ground
Notes:
1. Connect fixture supply and unit ground in accordance with
local and national codes.
2. Single voltage wiring only. Either 120V or 277V. Input and
output voltage must be the same.
3. DO NOT COMBINE THE INPUT POWER NEUTRAL
WITH THE LOAD NEUTRAL.
Switched Line(Not Used)
Neutral
Ground
Notes:
1. Connect fixture supply and unit ground in accordance with
local and national codes.
2. Single voltage wiring only. Either 120V or 277V. Input and
output voltage must be the same.
3. DO NOT COMBINE THE INPUT POWER NEUTRAL
WITH THE LOAD NEUTRAL.
Fax: (800) 316-4515
www.emergi-lite.com
EMIU 125/250/400W Mini Inverter
Output Wiring
Line
Neutral
Lighting Load
Fluorescent, LED,
Incandescent
Output Wiring
Line
Neutral
Lighting Load
Fluorescent, LED,
Incandescent
06/18 750.1782 Rev. J
6/12