Instruction Manual
Locating the Thermostat
The room temperature sensor is located in the Thermostat. For proper operation, the sensor must
be exposed to the heat produced by the stove. The preferred mounting locations include: on an
inside wall, away from the direct air stream of the convection blower, and away from radiant heat
produced by the stove. Note that the Thermostat does not have to be within the same room as the
stove. For example, a coal furnace ducted to the return air plenum of an oil or gas furnace will
give good results if the Thermostat is mounted next to the oil/gas furnace thermostat.
Connect Thermostat to Control Module
25 ft. Thermostat Cord
Connect the Thermostat cable to the THERMOSTAT connector on the Control Module and the
Connector on the rear of the TS2 Thermostat.
Room Over-Temperature Cutout
DISPLAY
HiTemp
STOP
Automation Correct LLC
Coal-trol Digital™ – Model TS2 THERMOSTAT
The provided 25ft. cord may be extended with an 8
pin, RJ45 to RJ45 coupler and/or standard computer
network cable. The cable must be a 'through' type,
not a crossover type. Note: The Coal-trol thermostat
and Power Module cannot be connected to computer
networks through this cable.
ACTION
The temperature sensor in the
thermostat
has
detected
room temperature above 98°F/
37°C and has disabled the
Stoker motor, combustion air
motor
and
the
Convection
Blower. If installed, the Power
Vent motor continues to run.
CAUTION: Before proceeding,
investigate the cause of the
over-temperature condition.
Press MENU button to Reset.
6/2006 R0
NOTE
a
The STATUS indicator light
blinks every second.
The HI TEMP display may
indicate a problem with your
stove, chimney, or Coal-trol
Digital System.
The thermostat will not allow
the MENU button to reset the
thermostat
temperature is less than 97°F/
35°C
www.automationcorrect.com
Page 5
until
the
room