Dynalite DBC410 Manual de instalação - Página 4

Procurar online ou descarregar pdf Manual de instalação para Controlador Dynalite DBC410. Dynalite DBC410 8 páginas. 4 x 10a hf ballast controller

mounting

4
DBC410 Installation Manual Rev K.docx
Select a Suitable Location
This device is designed for indoor use only. If
installing in an external location, the DBC410
must be housed in a suitable well-ventilated
enclosure. Choose a dry location, that will be
accessible after the installation is complete.
The DBC410 should be mounted vertically,
the right way up. The DBC410 requires an
air gap of 100mm on each side and at the top
and bottom of the device. This air gap is
required to ensure serviceability of the
DBC410 without complete removal from the
mounting surface.
some mechanical noise.
account when deciding the mounting location.
Fixing the Device
The DBC410 has four mounting brackets that
attach to the rear of the enclosure.
brackets are designed to accommodate 4
fixing screws up to 8mm diameter.
DBC410 can be fixed to the wall without
opening the cabinet or removing covers.
Make sure no dust or other debris enters the
device during installation. Do not leave the
front cover off for any length of time.
Excessive dust and dirt can degrade the
cooling of internal components.
Allow for Cable Entry
Supply, load and load control cables enter the
enclosure at the top. If these cables are fed
from below the mounting position, they
should be routed around the enclosure to
enter at the top. An alternative method is to
stand the enclosure off from the mounting
surface by mounting it on a cable tray or a
Unistrut style product. The cables can then
be routed between the enclosure and the
mounting surface, and enter the enclosure via
the cutout provided on the mounting face.
The control cables enter at the bottom of the
enclosure. Control cables should never be
run in the mains voltage sections of the
enclosure.
This device may emit
Take this into
The
The