AutomationDirect SOLO SL4848-CV Manual de início rápido - Página 2

Procurar online ou descarregar pdf Manual de início rápido para Controlador de temperatura AutomationDirect SOLO SL4848-CV. AutomationDirect SOLO SL4848-CV 4 páginas.

6
Mounting Instructions
SOLO temperature controllers can be mounted through a cutout in an enclosure or panel by using the dimen-
sions shown in Section 5. The directions for mounting the controller through a cutout are:
1. Insert the temperature controller through the panel cutout.
2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm
mounting screw in the mounting bracket.
3. Insert the mounting bracket into the mounting groove at the top and bottom of the controller, and push the
mounting bracket forward until the bracket stops.
4. Tighten top and bottom screws evenly to secure temperature controller in place.
1
7
Terminal Identification
WARNING! Electric shock danger
To prevent electric shock, do not connect AC power to your device until all input and output
connections are completed.
SL4848-RR
SL4848-VR
SL4848-CR
Sensor Input
0 – 10 VDC
4 – 20 mA
2-wire RTD
Thermocouple
3-wire RTD
All manuals and user guides at all-guides.com
4
2 2
3
SL4848-LR
SL4848-LV
SL4848-VV
SL4848-CV
Power Input
AC Powered
Models
DC Powered
Models
24 VDC power for models with
–D suffix only
8
Display, LED and Key Pad
PV Display: To display the process value or parameter type.
SV Display: To display the set point, parameter operation read value
SOLO
4848
manipulated variable or set value of the parameter.
PV
C
AT: Auto-tuning LED, flashes when the Auto-tuning operation is ON.
F
OUT1 / OUT2: Output LED, lights when the output is ON.
SV
ALM: Alarm output LED, lights when one of the alarms is on.
AT
OUT1
OUT2
ALM
°C, °F: Temperature unit LED. °C: Celsius °F: Fahrenheit
Set Button: Press this key to select the desired function mode and
SET
confirm the setting value.
Rotate Button: Press this key to select parameters within the function
mode.
Down Button: Press this key to decrease values displayed on the SV
display. Hold down this key to speed up the decrement.
Up Button: Press this key to increase values displayed on the SV
display. Hold down this key to speed up the increment.
9
Key Pad Operation
SET
Press for less
than 3 sec.
Regulation
Operation Mode
Mode
SET
Regulation
Operation
Parameters
Parameters
The SOLO temperature controller has three function modes: Initial Setting mode, Operation mode and Regulation
mode. When power is first applied to the temperature controller, the module information splash screen appears.
This screen shows the firmware version on the PV display and the two output types for that particular model on
the SV display. After three seconds, the controller will automatically proceed to the Operation mode main screen.
;
Press and hold the
button for three seconds to go into the Initial Setting mode. Press the
than three seconds to access the Regulation mode. Press the
modes to access the individual parameters for each function mode. Use the
;
individual parameter values. Pressing the
button saves the parameter values. Press the
to return the controller to the Operation mode.
10
Reset to Factory Default Instructions
All of the following set up instructions are for setting up a controller from the factory defaults. If the appli-
cation for a controller needs to be changed, reset the controller to factory default using the following
steps.
'
loC
1. Press the
button until the parameter
;
button.
,
.
2. Press and hold the
and
buttons simultaneously for one second and release.
'
3. Press the
button repeatedly until the PV display shows
1357
;
on the SV display to
. Press the
button.
4. Cycle power on the Controller to reset to factory default mode. All user set values are erased.
11-1
Thermocouple or RTD Input
1. Access the Initial Setup mode by pressing and holding the
inpt
,
.
, use the
and
buttons to select the value that corresponds to the thermocouple or RTD type
that will be attached to the controller. See the table below for specifications. Press the
selected value. The controller will display the module information splash screen for three seconds and then return
to the main screen.
;
2. Press the
button for three seconds again. Press the
,
.
C
the
and
buttons to select either
for Centigrade or
to save the selected value. The controller will display the module information splash screen for three seconds and
then return to the main screen.
;
3. Press the
button for three seconds again. Press the
,
.
appears. Use the
and
buttons to set the maximum value of the operational temperature range. In oper-
ation, if the PV value is higher than the TP-H value, the PV display flashes to indicate an error and the controller
outputs shut off. The SV value cannot exceed the TP-H value. Press the
'
tp-l
Press the
button to access the
parameter. Use the
of the operational temperature range. In operation, if the PV value is lower than the TP-L value, the PV display
flashes to indicate an error and the controller outputs shut off. The SV value cannot be set lower than the TP-L
;
value. Press the
button twice to save the selected value and return to the controller main screen.
'
4. Press the
button repeatedly until the parameter
0
1
either
for a whole degree or
for a tenth degree temperature display.* Press the
the selected value and return to the controller main screen.
5. If the input temperature from the thermocouple or RTD needs to be adjusted, press the
'
than 3 seconds. Press the
button repeatedly until the parameter
buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the
twice to save the selected value and return to the controller main screen.
*Note: The decimal point display cannot be adjusted for B, S, and R type thermocouples.
Thermocouple* Type and Temperature Range
Input Temperature Sensor Type
Thermocouple TXK type
Thermocouple U type
Thermocouple L type
Thermocouple B type
Thermocouple S type
Thermocouple R type
Thermocouple N type
Thermocouple E type
Thermocouple T type
Thermocouple J type
Thermocouple K type
RTD Type and Temperature Range
Input Temperature Sensor Type
Platinum Resistance (Pt100)
Platinum Resistance (JPt100)
*Note: Use only ungrounded thermocouples.
SET
Hold for 3 sec.
Initial Setting
Mode
SET
Initial Setting
Parameters
;
button for less
'
button while inside any of the three function
.
,
and
buttons to change the
;
button again
.
loC1
appears. Use the
button to select
. Press the
pass
,
. Use the
button to change the value
;
button for three seconds. In the parameter
;
button to save the
'
tpun
button to access the
parameter. Use
f
;
for Fahrenheit display. Press the
'
tp-H
button repeatedly until the
parameter
;
button to save the selected value.
,
.
and
buttons to set the minimum value
sp
,
.
appears. Use the
and
buttons to select
;
button twice to save
;
button for less
tpof
,
appears. Use the
and
;
LED Display
Temperature Range
txk
-328 ~ 1472°F (-200 ~ 800°C)
u
-328 ~ 932°F (-200 ~ 500°C)
l
-328 ~ 1562°F (-200 ~ 850°C)
b
-212 ~ 3272°F (100 ~ 1800°C)
s
32 ~ 3092°F (0 ~ 1700°C)
r
32 ~ 3092°F (0 ~ 1700°C)
n
-328 ~ 2372°F (-200 ~ 1300°C)
e
32 ~ 1112°F (0 ~ 600°C)
t
-328 ~ 752°F (-200 ~ 400°C)
j
-148 ~ 2192°F (-100 ~ 1200°C)
k
-328 ~ 2372°F (-200 ~ 1300°C)
LED Display
Temperature Range
pt
-328 ~ 1112°F (-200 ~ 600°C)
jpt
-4 ~ 752°F (-20 ~ 400°C)
button
.
button