Input Specifications
Inputs per Module
Input Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Input Type
Maximum Continuous Overload
Input Impedance
Hardware Filter Characteristics
Sample Duration Time
All Channel Update Rate
Open Circuit Detection Time
Conversion Method
Accuracy vs. Temperature
Maximum Inaccuracy
Linearity Error
Input Stability and Repeatability
Full Scale Calibration Error
(including offset)
Offset Calibration Error
Max Crosstalk at DC, 50Hz and
60Hz
External Power Supply Required
2
www.productivity1000.com
4
0–10 VDC
13-bit
0–10 VDC = 1.22 mV per count
(1LSB = 1 count)
0–8191 counts
Single-ended (1 common)
±100VDC
200k:
Low Pass, -3dB @ 100Hz
4ms per channel
(does not include ladder scan time)
20ms
Zero reading within 100ms
Successive approximation
±75PPM / ºC maximum
0.5% of range
(including temperature drift)
±0.036% of range
Monotonic with no missing codes
±0.024% of range
±0.097% of range
±0.097% of range
±0.049% of range
24VDC (-20% / + 25%), 100mA
Output Specifications
Outputs per Module
Output Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Output Type
Output Value in Fault Mode
Load Impedance
Maximum Capacitive Load
Allowed Load Type
Maximum Inaccuracy
Full Scale Calibration Error
Offset Calibration Error
Accuracy vs. Temperature
Max Crosstalk at DC, 50/60Hz
Linearity Error (End to End)
Output Stability and
Repeatability
Output Ripple
Output Settling Time
All Channel Update Rate
Maximum Continuous Overload
Type of Output Protection
Output Signal at Power Up and
Power Down
Tech Support 770-844-4200
2
0–10 VDC
12-bit
0–10 VDC = 2.44 mV / count
1 LSB = 1 count
0–4095 counts
Voltage @ 10mA
0V
t1000:
0.01 µF
Grounded
0.5% of range
±0.2% of range
±0.2% of range
±75 PPM / °C maximum full-scale
calibration change (±0.0025% of range / °C)
-72dB, 1 LSB
±4 LSB max., (±0.1% of full scale)
Monotonic with no missing codes
±2% LSB after 10 min. warm up (typical)
±0.2% of full scale
0.3 ms max., 5µs min. (full scale range)
4ms
Outputs current limited to 40mA typical
Continuous overloads on multiple outputs
can damage the module.
0.1 µs Transient Suppressor
0V