General Specifications
Operating Temperature
Storage Temperature
Humidity
Environmental Air
Vibration
Shock
Field to Logic Side Isolation
Insulation Resistance
Heat Dissipation
Enclosure Type
Module Keying to Backplane
Module Location
Field Wiring
EU Directive
Connector Type (sold separately) 18-position removable terminal block
Weight
Agency Approvals
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com
0º to 60ºC (32º to 140ºF)
-20º to 70ºC (-4º to 158ºF)
5 to 95% (non-condensing)
No corrosive gases permitted
IEC60068-2-6 (Test Fc)
IEC60068-2-27 (Test Ea)
1800VAC applied for 1 second
> 10MΩ @ 500VDC
3250mW
Open Equipment
Electronic
Any I/O slot in a Productivity2000 System
Removable terminal block. Optional ZIPLink wiring
system See "Wiring Options" on page 5.
See the "EU Directive" topic in the Productivity Suite
Help File. Information can also be obtained at:
www.productivity2000.com
95g (3.4 oz)
UL61010-2-201 File E139594, Canada & USA
CE (EMC: EN61131-2*, SAFETY: EN61010-2-201)
Output Specifications
Output Channels
Output Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Output Type
Output Value in Fault Mode
Load Impedance
Maximum Capacitive Load
Allowed Load Type
Maximum Inaccuracy
Maximum Full Scale Calibration Error
(Not Including Offset)
Maximum Offset Calibration Error
Accuracy vs. Temperature
Max Crosstalk
Linearity Error (End to End)
Output Stability and Repeatability
Output Ripple
Output Settling Time
All Channel Update Rate
Maximum Continuous Overload
Type of Output Protection
Output Signal at Power Up and Power Down
External Power Supply Required
Tech Support 770-844-4200
4
0-10 V
12-bit
0-10 V = 2.44 mV per count
1 LSB = 1 count
0 to 4095 counts
Voltage sourcing at 10mA
0V
≥1000Ω
0.01 µF
Grounded
0.5% of range
(Including temperature drift)
±0.2% of range maximum
±0.2% of range maximum
±75 PPM / °C maximum full-scale calibration change
(±0.0025% of range / °C)
-72dB, 1 LSB
±4 LSB maximum, (±0.1% of full scale)
Monotonic with no missing codes
±2% LSB after 10 min. warm up (typical)
±0.1% of full scale
0.300 µs max., 5µs min. (full scale range)
1ms
Outputs current limited to 40mA typical
Continuous overloads on multiple outputs can damage
the module.
0.1 µF Transient Suppressor
0V
24VDC (-20% / +25%), 60mA